GENERAL
12
Pressure drop (mbar)
FLOW-RATE (m
3
/h)
0
2
4
6
8
10
12
14
16
18
20
0
5
10
15
20
25
b
IMPORTANT!
LEAVE THE SENSORS IN THEIR ORIGINAL POSITIONS EVEN IF THE BOILER IS CONFIGURED FOR USE IN A
CASCADED SYSTEM.
TAU 150 - 210 UNIT
This
TAU UNIT
boiler comes without a pump. A pump must therefore be provided as part of the installation.
In order to choose a pump of the right size, bear in mind the boiler’s water-side pressure drop, as shown in the figure below.
PUMPS
1
2
3
5
4
SENSORS INSERTED IN THEIR
SOCKETS IN THE BOILER:
- Flue gas temperature sensor (1)
- Safety thermostat temperature sensor (2)
- CH flow temperature sensor (3)
- Control temperature sensor (4)
- Flue gas thermostat (5)
Front view
Rear view
POSITIONING THE TEMPERATURE SENSORS
b
On initial start-up and at least every year, check that
all the pumps in the system rotate freely. Sludge and
lime scale can build up and cause seizure, especially
after long periods of disuse.
b
Protect all electrical devices under the pump before
you unscrew the inspection cap just in case water co-
mes out.
a
Never run the pump dry.