TECHNICAL ASSISTANCE SERVICE
43
- Press the
D
key.
The fan switches to minimum speed.
- Set CO
2
level by turning the adjuster screw (4) on the
gas valve with a TORX key. Turn anti-clockwise to redu-
ce CO
2
, clockwise to increase CO
2
.
Once the adjustments are complete, the combustion
parameters should be as specified in the tables below.
- Press
V
or
M
to return to normal functioning
mode.
- Re-check the maximum power calibration.
Once all adjustments have been made:
- Carefully screw the plug back on the combustion
analysis socket.
- Fit the top panel back on.
b
Adjustments must only be performed by the
r
Technical Assistance Service.
CO
2
values for functioning at
MAXIMUM POWER
4
+
-
TAU 150 UNIT TAU 210 UNIT
G20 (%)
9
9
G31 (%)
10,1
10,1