TECHNICAL ASSISTANCE SERVICE
53
Error
code via
QAA
Diagnostic
info
Description of error
Type of fault
System action
Procedure
129
84
Comburent air system
error
Maximum fan speed
exceeded
Safety shutdown
Check the air pressure
switch; check the air
intake pipe; check the
fan
129
85
Comburent air system
error
Fan speed below
minimum
Safety shutdown
Check the air pressure
switch; check the air
intake pipe; check the
fan
129
86
Comburent air system
error
Fan speed below
minimum
Safety shutdown
Check the air pressure
switch; check the air
intake pipe; check the
fan
129
87
Comburent air system
error
Fan speed below
minimum
Burner lockout
(permanent). Lockout
reset required
Check the air pressure
switch; check the air
intake pipe; check the
fan
129
89
Comburent air system
error
Fan speed below
minimum
Safety shutdown
Check the air pressure
switch; check the air
intake pipe; check the
fan
129
90
Comburent air system
error
Fan speed has fallen
below pre-purge speed
Burner lockout
(permanent). Lockout
reset required
Check the air pressure
switch; check the air
intake pipe; check the
fan
130
508
Flue gas temperature
threshold exceeded
TaAbschal parameter
(flue gas temperature
threshold for boiler
shutdown) exceeded
Safety shutdown
Check the flue gas vent;
check the temperature
sensor; check the
burner; check setting of
parameter 592
130
509
Flue gas temperature
threshold exceeded
TaBegrenz parameter
(flue gas temperature
threshold for reducing
heat output) exceeded
Message
Check the flue gas vent;
check the temperature
sensor; check the
burner; check setting of
parameter 591
132
77
Gas feed pressure
switch (GPS) tripped
The input has been
configured as a switch
that prevents start-up
(FaEinstellFlags2) and
the switch is open
Safety shutdown
Check for blockages in
the air/gas feed lines;
check the pressure
switch
132
92
Gas feed pressure
switch (GPS) tripped
The input has been
configured as a switch
that prevents start-up
(FaEinstellFlags2) and
the switch is open
Safety shutdown
Check for blockages in
the air/gas feed lines;
check the pressure
switch
132
93
Gas feed pressure
switch (GPS) tripped
The pressure switch
input has been
configured as a switch
that prevents start-up
(FaEinstellFlags2) and
the switch is open during
safety time
Safety shutdown
Check for blockages in
the air/gas feed lines;
check the pressure
switch
132
94
Gas feed pressure
switch (GPS) tripped
The pressure switch
input has been
configured as a switch
that prevents start-up
(FaEinstellFlags2) and
the switch is open during
safety time. Start-up
prevented for two hours
Safety shutdown
Check for blockages in
the air/gas feed lines;
check the pressure
switch
132
285
Gas feed pressure
switch (GPS) tripped
Shutdown at wrong time.
The error masking time
has been interrupted
Safety shutdown
Check for blockages in
the air/gas feed lines;
check the pressure
switch
133
101
No flame
The flame does not
appear at the end of the
safety time--> Repetition
Safety shutdown
Check the connections
to the burner
133
102
No flame
The flame does not
appear at the end of the
safety time
Burner lockout
(permanent). Lockout
reset required
Check the connections
to the burner