TECHNICAL ASSISTANCE SERVICE
58
COMPLETE LIST OF PARAMETERS
(*) Outdoor temperature sensor connected: set the room temperature reduced setpoint.
Outdoor temperature sensor not connected: set the boiler temperature reduced setpoint.
LIST OF END USER LEVEL PARAMETERS
Nr.
Characteristic
Range
U/M
Default
setting
1
Time of day
0…23.59
h/min
- - -
Setpoints
5 (*) Parameter not used if a room unit is connected
Room temperature reduced setpoint
10…30
°C
20
Boiler temperature reduced setpoint
30...Boiler temperature setpoint
CH circuit 1 program
11 Start of heating period 1
00:00…24:00
hh:mm
06:00
12 End of heating period 1
00:00…24:00
hh:mm
22:00
13 Start of heating period 2
00:00…24:00
hh:mm
24:00
14 End of heating period 2
00:00…24:00
hh:mm
24:00
15 Start of heating period 3
00:00…24:00
hh:mm
24:00
16 End of heating period 3
00:00…24:00
hh:mm
24:00
DHW program (only used in conjunction with a storage cylinder)
31 Start of preparation for DHW period 1
00:00…24:00
hh:mm
06:00
32 End of preparation for DHW period 1
00:00…24:00
hh:mm
22:00
33 Start of preparation for DHW period 2
00:00…24:00
hh:mm
24:00
34 End of preparation for DHW period 2
00:00…24:00
hh:mm
24:00
35 Start of preparation for DHW period 3
00:00…24:00
hh:mm
24:00
36 End of preparation for DHW period 3
00:00…24:00
hh:mm
24:00
45 Standard programs for central heating and domestic hot water.
(Press and hold the
-
and
+
keys simultaneously for 3 seconds)
No/Yes
- - -
No
516 Summer / Winter switching temperature
(30=switching disabled)
8…30
°C
20
520 PARAMETER FIXED IN THIS MODEL. DO NOT CHANGE SETTING
10
629 Maintenance alarm display
(0/1 =
disabled/enabled)
0
726 Maintenance code: a numeric value that identifies the cause of the error 0…255
0