Electrical Installation
Operating instructions RLD 91
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
Legend for figure 4.4.1.3 (REVCON
RLD B0/D0 with RHF-RA)
1.
Fusing in accordance with controller manual.
2.
It is not allowed to connect any other devices except the frequency inverter and the
power feedback unit behind the main magnetic switch.
Danger!
If this is not observed, you take the risk that, in the case of switching off the mains during feed-
back the power, the voltage in that sector may rise up to a dangerous level. This may destroy the
connected devices and perhaps also the inverter and/or the power feedback unit. To avoid such
situation, the power feedback unit is equipped with an overvoltage switch off, but nevertheless
this hint should be observed!
3.
RHF-RA module
4.
Cross section in accordance with the relevant VDE-rules.
5.
Fusing (Supply, <2A current input) in accordance with DIN VDE 0298 or short circuit
proof wiring.
6.
RFI-filter (optional):
At RFI-filter up to and including installation size RFI-RA23 is the connection to the
power feedback module realized by a PG-screw connection. This connection of the
RFI-filter must occur phase correct over the terminals -From Supply-. The terminals
-To Inverter- must be open.
7.
At these terminals one or more controllers (even with different power ratings) may be
attached, like it shown in figure 4.5.1. Even if several controllers are attached, the wires
have to be as
short and low impedance
as possible!
8.
The „ON“ or „RESET“ signal may be initiated via terminals 11 and 12:
Terminals 11 and 12: Positive pulse (12-24 V DC); practicable e.g. via PLC
(terminal 11 +, terminal 12 -).
9.
Fan supply: The power feedback modules of a higher power stage require the in the or-
dering code specified auxiliary voltage (230V or 115V).
Содержание RLD B
Страница 68: ...Installation Operating instructions RLD 67 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 1 Enclosure 0 340...
Страница 69: ...Installation 68 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 1 500...
Страница 70: ...Installation Operating instructions RLD 69 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 2 700...
Страница 71: ...Installation 70 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 3 800...
Страница 72: ...Installation Operating instructions RLD 71 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 3 801...
Страница 73: ...Installation 72 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 3 802...