Electrical Installation
Operating instructions RLD 95
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
4.4.2
Fan supply
Power feedback modules of a higher power stage are equipped with two terminals (blue
terminal = neutral [N], grey fuse terminal = phase [L]) for the supply of the internal fan(s).
The fuse inside the fuse terminal is installed for internal wire protection and of the follow-
ing type
2A medium 500V 5x30mm
.
4.4.3
Control wires
•
Connect the control wires to the terminal row X2 at the control plate of the power
feedback unit.
•
Don’t parallel control wires to interfering power wires.
•
Connect the screening of the control wires with an as big as possible surface to the
metal cable glands of the flange.
4.4.4
Control functions
The control terminal strip is placed on the control board and is indicated with X2. It is fit-
ted with a plug-in device for easy handling (see figure 4.4.4.2).
The control board must always be designed for the respective main circuit voltage. There-
fore the main circuit voltage (230 V, 380 V - 415 V, 440 V - 480 V, 500 V or 690 V) must
be declared with every order. This is also necessary for a possible exchange of the device.
From the control terminal strip the operating condition or rather the collective error can be
connected to extern. There is also the possibility to execute the external reset or the switch-
functions and to connect them with the controller or the PLC.
Содержание RLD B
Страница 68: ...Installation Operating instructions RLD 67 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 1 Enclosure 0 340...
Страница 69: ...Installation 68 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 1 500...
Страница 70: ...Installation Operating instructions RLD 69 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 2 700...
Страница 71: ...Installation 70 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 3 800...
Страница 72: ...Installation Operating instructions RLD 71 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 3 801...
Страница 73: ...Installation 72 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 3 802...