Electrical Installation
84 Operating instructions RLD
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
4.4
Connection
The supply line must be connected at the lead-through terminal at the bottom side of the
enclosure.
4.4.1
Power connection
Fusing (also refer to chapter 3.3.4)
•
The specifications of chapter 3.3.4 (fuses and wire cross sections) are recommenda-
tions and refer to the operation
– in cabinets and machines
– installation in cable ducts
– maximum ambient tempe40°C.
•
When choosing the cross section of the wire the voltage drop under load should be
considered (refer to chapter 3.4)
•
Protection of the wires at mains side (L1, L2, and L3):
– by commercial wire protection fuses.
– fuses have to be compliant with the relevant standards on site.
– rated voltage of the fuses have to be compliant with the voltage on site.
•
Protection of the power feedback unit at mains side (L1, L2, and L3):
– by commercial semiconductor fuses
– fuses have to be compliant with the relevant standards on site
– rated voltage of the fuses have to be compliant with the voltage on site
•
Protection of the power feedback unit at DC side (+UG, -UG):
– fuses are part of the power feedback unit (refer to chapter 3.3.4.2)
The erector/user of the plant bears the responsibility for the observance of further
relevant standards (e.g.: VDE 0113, VDE 0289 and so on).
Содержание RLD B
Страница 68: ...Installation Operating instructions RLD 67 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 1 Enclosure 0 340...
Страница 69: ...Installation 68 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 1 500...
Страница 70: ...Installation Operating instructions RLD 69 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 2 700...
Страница 71: ...Installation 70 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 3 800...
Страница 72: ...Installation Operating instructions RLD 71 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 3 801...
Страница 73: ...Installation 72 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 3 802...