Safety information
28 Operating instructions RLD
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
Unchoked compensation plants and resonance rise
Compensation plants are used in the centre of the power supply of a company. Disturb-
ances or damages at these plants have effects on the power supply and may result in inter-
rupted production processes.
Although this is no longer state of the art, many compensation plants are in operation with-
out any choking. The problems which result from a usage of such an unchoked compensa-
tion plant are manifold:
-
direct resonance
-
resonance rise
-
switching transients or
-
impairments of centralized ripple systems
The fact, that a company produces back effects to the power supply is not the only reason
for the creation of resonance. Decisive for the risk, to generate a resonance is the compen-
sation power at the medium voltage transformer. The higher this power is so higher is the
risk of resonance. The second important factor is the harmonic load of the medium voltage
level. This harmonic load is transmitted via the transformer and causes effects on the low
voltage level. Most often the limits were exceeded for the 5th harmonic component.
Содержание RLD B
Страница 68: ...Installation Operating instructions RLD 67 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 1 Enclosure 0 340...
Страница 69: ...Installation 68 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 1 500...
Страница 70: ...Installation Operating instructions RLD 69 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 2 700...
Страница 71: ...Installation 70 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 3 800...
Страница 72: ...Installation Operating instructions RLD 71 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 3 801...
Страница 73: ...Installation 72 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 3 802...