Configuration
110 Operating instructions RLD
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
e) Overvoltage supervision
Since the control board version 1.4.3 the device has an overvoltage supervision for the
mains which switches off the device in the case of a voltage level of approximately 1,15 x
U
N
and above. As an error message the error code 3 will be shown (see chapter 7.1). For
the differentiation of the error messages phase failure and overvoltage you have the possi-
bility to deactivate the phase-failure-supervision by removing the jumper J3 on the control
board. If after that a switch-off with the indication via the red and yellow LED (error code
3) happens, an overvoltage will be the reason of the switch-off then.
J3
J5 J6 J7 J8 LED Message
Evaluation (overvoltage)
—
X X — — Green 1.red Yellow Overvoltage a/o phase failure/commutation
error
—
X X 0 — Green —
Yellow Overvoltage
0
X X — — Green 1.red Yellow Overvoltage a/o phase failure/commutation
error
0
X X 0 — Green —
Yellow Overvoltage
0
X X 0 — Green 1.red Yellow Constant phase failure
Remark:
0 Jumper open
— Jumper closed
X Jumper random
Standard adjustment of the device
Autostart and no switching off in case of phase failure
Содержание RLD B
Страница 68: ...Installation Operating instructions RLD 67 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 1 Enclosure 0 340...
Страница 69: ...Installation 68 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 1 500...
Страница 70: ...Installation Operating instructions RLD 69 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 2 700...
Страница 71: ...Installation 70 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 3 800...
Страница 72: ...Installation Operating instructions RLD 71 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 3 801...
Страница 73: ...Installation 72 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 3 802...