Technical data
Operating instructions RLD 49
ELTROPLAN
-
REVCON
Elektrotechnische Anlagen GmbH
Series fuses REVCON RLD B1/D1
REVCON
®
- type
RLD B1/D1
Max. fuse AC
Connection terminal
and max. Cross section
of the supply line*
7-400-50-0-A
Siba 5012406.20 20A 690V 10x38mm
ES
25mm²
13-400-50-0-A
Siba 5017906.30 30A 690V 14x51mm
ES
25mm²
22-400-50-0-A
Siba 5012406.50 50A 690V 14x51mm
ES
25mm²
33-400-50-0-A
Siba 5014006.80 80A 690V 22x58mm
ES
25mm²
45-400-50-0-A
Siba 5014006.100 100A 690V 22x58mm
ES 25mm²
Table 3.6.1.11
ES
≅
end sleeve for strands
CL
≅
Cable lug
* At the fuse holder respective disconnector
Internal fuses REVCON RLD B0
The power feedback unit is equipped with semiconductor fuses according to the following
tables (refer to figure 4.4.1.1 position 8. The listed manufacturer is recommended, but nat-
urally also comparative fuses of other manufacturer (e.g. Jean Müller, Ferraz, and
Bussmann) are suitable.
Stop!
If semiconductor fuses trip, please get in contact with ELTROPLAN-REVCON immediately, as
possibly further protective measures have tripped. If internal fuses are exchanged, please verify
that only the original types are used for replacement.
Danger!
Before replacing a fuse, switch off all voltages!
REVCON
®
- type
DC-fuses
(use fast acting semiconductor fuses only)
RLD B0 4-230-50-0-A
Siba 5012406.20 20A 690V 14x51mm
RLD B0 7-230-50-0-A
Siba 5012406.32 32A 690V 14x51mm
RLD B0 12-230-50-0-A
Siba 5014006.63 63A 690V 14x51mm
RLD B0 18-230-50-0-A
Siba 5014006.80 80A 690V 22x58mm
RLD B0 22-230-50-0-A
Siba 5014206.135 135A 690V 22x58mm
RLD B0 38-230-50-230-A
Siba 2018920.250 250A 690V NH 00
RLD B0 50-230-50-230-A
Siba 2018920.350 350A 690V NH 00
RLD B0 75-230-50-230-A
Siba 2018920.400 400A 690V NH 00
RLD B0 90-230-50-230-A
Siba 2077132.500 500A 1250V NH 01
RLD B0 115-230-50-230-A
Siba 2071332.630 630A 1110V NH 01
RLD B0 145-230-50-230-A
Siba 2071332.630 630A 1110V NH 01
RLD B0 200-230-50-230-A
Siba 2072332.800 800A 1100V NH 02
Table 3.6.1.12
STOP
Содержание RLD B
Страница 68: ...Installation Operating instructions RLD 67 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 1 Enclosure 0 340...
Страница 69: ...Installation 68 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 2 Enclosure 1 500...
Страница 70: ...Installation Operating instructions RLD 69 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 3 Enclosure 2 700...
Страница 71: ...Installation 70 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 4 Enclosure 3 800...
Страница 72: ...Installation Operating instructions RLD 71 ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 5 Enclosure 3 801...
Страница 73: ...Installation 72 Operating instructions RLD ELTROPLAN REVCON Elektrotechnische Anlagen GmbH 6 Enclosure 3 802...