Parameter explanations V2.1_V2.6
2
IRA_B8_EN_2V2_REC_102-020401137
41/ 56
→ Reduced OM
The relay is active as long as an operating mode with
reduced
opening width
is activated.
→ Power failure
The relay is active as long as there is no mains voltage and
the control unit is operated by battery.
▪ If
Parameter → Drive → Power failure
is configured for
Bat-
tery operation
, the relay remains active until the control unit
changes to sleep mode.
▪ If
Parameter → Drive → Power failure
is configured for
Emergency operation
, the relay only remains active during
the action configured with
Parameter → Emergency opera-
tion battery
. Afterwards the control unit change to sleep
mode and the relay is deactivated.
→ Locking error
The relay is active as long as a locking or unlocking error has
been detected.
→ Battery error
Relay active during a battery error.
▪ Depending on door type the battery might only be tested
once per hour.
Accordingly, it can last up to an hour until a battery defect
is displayed.
→ ELS error
Relay active during an ELS error.
→ Emergency stop/open
Relay active while connection
Emergency stop
or
Emergency
open
is cut.
→ AKI/AKA time
The relay is active while an AKI or AKA triggering signal re-
mains activated.
▪ The time until the output is activated can be adjusted with
Parameter → Miscellaneous → Alarm display → Time acti-
vation
.
→ SÖK/NSK
The relay is active while an SÖK or NSK signal is triggered.
→ CAN connection
The relay is active as long as there is a problem with the CAN
connection between STM and FEM1.
→ Error RED test
The relay is activated.
→ Maintenance is due
The relay is activated when 95% of the maintenance target
value is reached.
→ Maintenance time ex-
ceeded
The relay is activated when 105% of the maintenance target
value is reached.
→ Redundancy test
The relay is activated while a redundancy test is being carried
out.
Содержание system 20
Страница 1: ...record system 20 B8 Parameter explanations Translation of the original manual ...
Страница 48: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 48 56 ...
Страница 50: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 50 56 ...
Страница 51: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 51 56 Parameter overview STM 21 3 3 ...
Страница 52: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 52 56 ...
Страница 53: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 53 56 Parameter overview STM 21 RED 3 4 ...
Страница 54: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 54 56 ...
Страница 55: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 55 56 Parameter overview FEM 3 5 ...
Страница 56: ...Parameter overview V2 1_V2 6 3 IRA_B8_EN_2V2_REC_102 020401137 56 56 ...