UMHPI
Industrial inverter air/water heat pumps with axial fans
35
11.10
CONFIGURATION PARAMETERS – Module “GI”
As for UMHPI V units and in case of installation of the optional kit module (GI2) on UMHPI units, it is possible to manage the
following additional functions. Such parameters can be activated and/or adjusted by the installer from of
CB master controller
menu
mounted on the front panel of the unit.
Parameter
Description
Unit
Default
Range
Visibility
Allowed Configurations
Notes
H24
Configuration of ST3E
input
/ 41 0÷49
INSTALLER
0 = input not assigned
6 = DHW temperature sensor
41 = water plant temp. remote sensor
Terminals: AI1E-AI1E
H49 = 0.
(3)
H28
Configuration of ST7E
input
/ 0 0÷49
INSTALLER
0 = input not assigned
6 = DHW temperature sensor
41 = water plant temp. remote sensor
Terminals: ADI1E-ADI1E ù
H51 = 0.
(3)
H49
Configuration of DI4E
input
/ 0 0÷30
INSTALLER
0 = input not assigned
19= Ambient thermostat
26 = Double set-point
28 = sanitary thermoregulation call
from digital input
Terminals: ADI1E-ADI1E
H24 = 0.
The input is used only in the absence
of the Evo Touch control panel.
H51
Configuration of DI6E
input
/ 0 0÷30
INSTALLER
0 = input not assigned
19= Ambient thermostat
26 = Double set-point
28 = sanitary thermoregulation call
from digital input
ADI1E-ADI1E terminals
H28 = 0.
H63
Configuration of DO1E
input
/ 26 0÷44
INSTALLER
0 = input not assigned
21 = Defrosting signalization
24= Alarm signalization (notification)
25 = double set point valve
26 = DHW auxiliary electric heater
29 = Boiler
31 = Plant season signalization
42 = Unique pump in the network
43 = Relaunching (secondary) pump
DO1EN-DO1E terminals
H64
Configuration of DO2E
/
22
0÷44
INSTALLER
DO2EN-DO2E terminals
(3)
H65
Configuration of DO3E
/
29
0÷44
INSTALLER
DO3EN-DO3E terminals
(3)
H66
Configuration of DO4E
/
0
0÷44
INSTALLER
DO4EN-DO4E terminals
(3)
H67
Configuration of DO5E
/
0
0÷44
INSTALLER
DO5EN-DO5E terminals
H68
Configuration of OC1E
/
25
0÷44
INSTALLER
NC1E-N1E-NO1E terminals.
H69
Configuration of OC2E
/
31
0÷44
INSTALLER
NC1E-N1E-NO1E terminals
(3)
Is not selectable for UMHPI V units.
(
4)
Adjustable with Evo Touch accessory.
11.11
CONFIGURATION PARAMETERS OF THE HEATING DEVICES – Mod Gi
CONFIGURATION PARAMETERS OF THE HEATING DEVICES
Parameter
Description
Unit
Default
Range
Visibility
Allowed configuration
Note
r02
Setpoint of anti-freeze heater in
heating mode
°C 3 3÷6 INSTALLER
r03
Setpoint of anti-freeze heater in
cooling mode
°C 3 3÷6 INSTALLER
r06
Differential of anti-freeze
electric heater
°C 2.0 0.0÷25.5
INSTALLER
(5)
r08
Upper limit during in
substitution operation
°C
according to
the model
-16÷50 INSTALLER
Respect the condition
r22
≥
r28
≥
r08
r09
Hysteresis for heat pump
lockout
°C 1.0 0.0÷25.5
INSTALLER
r10
Enabling the auxiliary electric
heater of the plant
/ 0 0÷1 INSTALLER
0 = deactivated function
1 = enabled function
r11
Differential of the plant auxiliary
electric heater
°C 0.5 0.0÷25.5
INSTALLER
r12
Auxiliary plant/HP electric
heater activation delay
min 10 0÷255 INSTALLER
r13
Auxiliary heater deactivation
delay
min 10 0÷255 INSTALLER
r14
Exclusive operation of the
electric-heaters
/ 0 0÷1 INSTALLER
0 = Simultaneous enabling of the electric heaters
1 = Exclusive enablement of the electric heaters
r15
DHW auxiliary electric heater
enablement
/ 0 0÷2 INSTALLER
0 = deactivated function
1 = enabled function
2 = Operation of auxiliary plant-side electric
only if H83=1
r16
DHW auxiliary heater/heat pump
activation delay
min 15 0÷255 INSTALLER
r19
Activation time of drain pan
heaters from last defrost
min 0 0÷255 INSTALLER
0= activation of E-heater independently of
defrosting.
r20
E-heater priority utilization
/
1
0÷1
INSTALLER
0 = priority for plant-side
1 = priority for DHW side
Only if r14 = 1
r21
Plant side mitigation enabling
with heaters in defrost
/ 0 0÷1 INSTALLER
0 = deactivated function
1 = enabled function
r22
Upper limit joint operation area I
°C
according to
the model
-127÷127 INSTALLER
Respect the condition
r22
≥
r28
≥
r08
r23
Type of boiler utilization
/
60
0÷6
INSTALLER
r24
Type of use of the auxiliary
heaters
/ 3 0÷3 INSTALLER
r25
Disinfection Setpoint (anti-
legionella)
°C 80 0÷100 INSTALLER
Adjustable parameters
by mean of remote
control panel
Evo
Содержание UMHPI
Страница 1: ...Chiller and Heat Pumps UMHPI Controller USER MANUAL UMHPI on board electronic user controller ...
Страница 2: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ...FAE0FA000BZ 00 06 2018 bit ly rdzwebsite ...