UMHPI
Industrial inverter air/water heat pumps with axial fans
23
Before proceeding, the equation must be: in continuous mode, fulfilled or unfulfilled respectively for
v11
minutes
(fulfillment) and
v12
minutes (unfulfillment). At the power-on, the unit turns on with unfulfilled equation.
7.16.3
Vapor injection valve (VEIV)
Even after the fulfillment of one of the two equations (Eq.1 or Eq.2) the VEIV valve must remain closed until the below condition is
met also:
(Eq.3) DSH >
v13
Before proceeding, the equation must be fulfilled or unfulfilled, in continuous mode respectively
v14/v15
minutes (fulfilled) and
v16/v17
minutes (unfulfilled).
After the condition fulfillment, the valve will be managed following the superheating given by:
−
ISH
(superheating of vapor injection) =
T1
(detected) -
T2
(resulted)
The recognition of the situation of the preconditioned unfulfillment DHS value will close the VEIV valve. At the shutdown of the
whole compressors the VEIV valve will be closed and the above control logic will resume only after their re-ignition.
In the case of multi compressor systems in addition to the VEIV valve, each compressor will have its own ON/OFF valve to allow
the vapor injection only when the corresponding compressor is turned on and not only to the fulfillment of the above conditions.
The valve that enables vapor injection will turn on only when the compressor is switched on for at least
v18
seconds and the
injection is active.
•
Initial steps
: Set the number of initial steps of the valve. At the first opening of the valve, the superheat control is bypassed
for Pa
v18
seconds and the valve positioned with this initial value. After the end of
v18
seconds the superheating control
will be activated.
•
Control algorithm of the vapor injection valve
: The control is of the PID type (proportional/integral/derivative) operates on
the process variable ISH. The valve opening may vary between the maximum (
v22
) and the minimum steps (depending on
the operating mode).
8
ACTIVABLE LOGIC FUNCTIONS WITH GI- MODULE FOR PLANT MANAGEMENT (optional)
Wherever the GI optional plant management kit is present, there is a second controller located inside the electrical board that acts
as expansion module of the I/O resources. With this second controller (SL1), it is therefore possible to increase the number of logic
functions managed by the main controller; in particular, these logic functions are used for management the plant, as we described
below. The following functions can be activated by the controller of the Master unit which is located on its front panel.
8.1
AUXILIARY ELECTRIC HEATERS
In some plant systems configurations, it could be necessary the use an auxiliary electric heater for the system and/or DHW sides.
To define the mode of using of the auxiliary electric heaters for plant system and DHW side, you must set the parameter “
r24”
as
below
.
-
r24=0
Auxiliary electric heaters not used;
-
r24=1
Utilization only of the auxiliary electric heater of the plant side;
-
r24=2
Utilization only of the auxiliary DHW electric heater;
-
r24=3
Utilization of both auxiliary electric heaters of plant side and of domestic (sanitary) hot water production.
To change the parameters, please see paragraph 11.11.
8.1.1
AUXILIARY ELECTRIC HEATER THE PLANT SYSTEM
In some configurations of plants, the use of an auxiliary electric heater for the plant system side could be necessary.
If the temperature of regulation remains below the
water setpoint in heating (Hea) - 0.5°C
for a period of time equal to
r12
, the
auxiliary electric heater will be activated depending on the in joint or in substitution operation of the unit indicated in Paragraph
8.2. The electric heater turns off after reaching the setpoint (taking into account of an eventual offset set with the parameters
r29
or
r30
(check Paragraph 8.3.6).
If the temperature of regulation remains less than
water setpoint – r11(°C)
and the unit is blocked that is caused by an error-
alarm, the electric heater will be activated. Then it will turn off when the lock-alarm is resolved.
To activate this function you should set the parameters
CnF
and
rE
by getting access with the service password:
Parameter
Unit
Value
Description
Terminals
Notes
*H63
Num
22
(default)
Undervoltage output plant
system auxiliary E-heater
DO1E(Live)
DO1EN (Neutral)
Undervoltage output 230V ac, 50Hz, 5A resistive, 1A inductive.
Should be connected to the relay coil in order to get a free
contact.
r10
Num
1
Enablement of the function
-
-
r11
°C
0.5
(default)
(Delta of the auxiliary electric
heaters in heating operation)
- -
r12
Min
10
(default)
Activation delay of auxiliary
electric heater
- -
r24
Num 1
o
3
Type of use of the electric
heater
- -
Содержание UMHPI
Страница 1: ...Chiller and Heat Pumps UMHPI Controller USER MANUAL UMHPI on board electronic user controller ...
Страница 2: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ...FAE0FA000BZ 00 06 2018 bit ly rdzwebsite ...