UMHPI
Industrial inverter air/water heat pumps with axial fans
18
If the DHW temperature is below the set point value (adjustable by entering the
PRG->Set->SAN
menu), the unit activates the
sanitary valve and the compressor is set at the maximum frequency starting the modulation at one degree before the set value
and it stops at one degree after the set value. Once reached the set point value, the valve switches to the stand-by mode and the
compressor works normally.
While shifting from user’s to domestic hot (sanitary) water, the operating sensor changes from “outlet water sensor” to “sanitary
tank sensor”. While shifting from the winter operating mode to the sanitary operating mode, the compressor does not switch off,
and reaches the maximum established frequency that to be controlled; on the other hand, while shifting from the summer
operating mode to the sanitary operating mode, the compressor is switched off to wait for the safety timing.
The defrosting during winter operation mode is always performed on the user side, never on the sanitary water tank.
Note:
-
If
H10 = 1
. The remote turning off the unit (remote onoff), or by the on board unit controller, or by a remote control board does
not affect the sanitary operating mode. The unit starts in sanitary mode as setting priority when it’s powered on. The on board
unit display shows the temperature measured by the sensor placed inside the sanitary water tank. Once the sanitary cycle is
completed, the display returns to show the temperature of the outlet water sensor.
If the remote ON-OFF digital input (onoff-onoff terminals) is open, with the enabling of the domestic hot water production (
H10=1
and
H20=6
), the display on-board unit shows the item "
SAN
". Once the sanitary cycle is concluded, the display returns to show the
code "
E00
" indicating that the remote ON-OFF contact is open.
- If H10
= 2
, the remote on-off function disenables the production of domestic hot water and the operations of the heat pump in
heating and cooling on plant side.
Example
of a
ctivation of this function
:
H10 =
1
H19 =
6
DHW temperature sensor [terminals: SAN – SAN]
H61 =
6(default)
In case of using a 3-way changeover valve with 3 contacts for power supply [terminals: NO1 – N - NC1]
In case of using a 3-way changeover valve with 2 contacts for power supply (with spring return),
[terminals: NO1 – N]
•
Closed contact NO1
means that the valve is energized and diverts the water flow to the DHW tank.
•
Open contact NO1
means that the valve is de-energized and diverts the water flow to users.
For the models UMHPI 60, this function can be activated only with the presence of the optional “GI” module.
7.12.1
MEMORY OF THE SENSOR IN HEATING MODE
In the case of commutation from water users to the domestic hot water, the temperature sensor changes from a "water outlet
temperature sensor" to a "water tank temperature sensor". For such reason, in heating mode, the last value read by the sensor
will be memorized before changing to DHW mode.
When the DHW thermoregulation is reached, the reference temperature on the plant side will take the value which is previously
memorized.
The memory function will be interrupted:
-
When the temperature detected by the sensor becomes lower than the memorized value;
-
Or after a period of time equal to
b06
seconds (default 45 seconds).
For each
UMHPI
unit (except the last unit of the cascade), you must implement a relay (not included), controlled by the output
230VAC
NO1
and
N
located on the terminal block, that can enable through its free contacts
COM
and
NO
the
ADI2-ADI2
digital
input of the successive unit in the cascade. For such configuration you may refer to the wiring diagram below.
Содержание UMHPI
Страница 1: ...Chiller and Heat Pumps UMHPI Controller USER MANUAL UMHPI on board electronic user controller ...
Страница 2: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ...FAE0FA000BZ 00 06 2018 bit ly rdzwebsite ...