UMHPI
Industrial inverter air/water heat pumps with axial fans
8
Level 0 (
U
) = always appearing
Level 1 (
M
) = it appears if you enter the maintainer or manufacturer password
Level 2 (
C
) = it appears if you enter the manufacturer password
Level 3 (
A
) = it appears only via Modbus
6.2
ANALOG INPUTS
By entering the maintainer password in the menu of analog inputs "tP", at the level 1 of the menu structure diagram of the on-
board control panel, you can read the values of the current probes:
tp
DESCRIPTION
Unit
t01
Water inlet temperature
(°C)
t02 Water
outlet
temperature
(°C)
t03
Compressor inlet temperature
(°C)
t04
Compressor outlet (discharge) temperature
(°C)
t05 High
pressure
(bar)
t06 Low
pressure
(bar)
t07
Outdoor air temperature
(°C)
t08
DHW temperature (if DHW is enabled)
(°C)
t09
DHW temperature (if DHW production is enabled)
(°C)
*t11
Plant circuit remote temperature sensor (if enabled)
(°C)
**t15 Injection
pressure
(bar)
**t17 Injection
temperature
(°C)
(*) Present in the UMHPI V models or with the optional kit mod.
Gi
in the the models UMHPI.
(**) Present in the UMHPI V models
6.3
PARAMETERS CATEGORIES
The parameters are classified into groups, each group is identified by a 3-digit code, while the index of each parameter is preceded
by a letter.
DESCRIPTION
GROUP IDENTIFICATION CODE
PARAMETER INDEX
VISIBILITY
Configuration CnF
H-
USER/INSTALLER
Compressor CP
C-
INSTALLER
Fan-motor FAn
F-
INSTALLER
Alarms ALL
A-
INSTALLER
Regulation Re
b-
INSTALLER
Pump PUP
P-
INSTALLER
Electric heater
Fro
r-
INSTALLER
Defrosting dFr
d-
INSTALLER
Electronic expansion valve
EEu
U-
INSTALLER
Offset OFF
o-
INSTALLER
**Mixer valve
rAd
i-
INSTALLER
**Solar SUn
S-
INSTALLER
*Vapor injection
Eiu
u-
INSTALLER
Inverter compressors
nCP
n-
INSTALLER
**DHW preparer
AcS
Ac-
USER/INSTALLER
(*) Parameters present in UMHPI V series
(**) Parameters present with the optional KIE module
6.4
ADJUSTABLE SETPOINT BY THE USER
SETPOINT
DESCRIPTION
UNIT
DEFAULT
RANGE
Coo
Summer mode first setpoint
°C
7.0
5÷18
Hea
Winter mode first setpoint
°C
45.0 35÷57
*San
DHW mode setpoint
°C
48.0 25÷57
Co2
Summer mode second setpoint
°C
18.0
Coo
÷23
He2
Winter mode second setpoint
°C
35.0 25÷
Hea
**rCO
Mixer valve setpoint in Summer mode
°C
15.0 -50.0÷80.0
rHE
Mixer valve setpoint in Winter mode
°C
30.0 -50.0÷80.0
ACS
DHW instantaneous production setpoint
°C
45.0 0.0÷80.0
(*) Adjustable Setpoint if the DHW function is enabled.
(**) Adjustable Setpoint if the optional KIE module is included.
Содержание UMHPI
Страница 1: ...Chiller and Heat Pumps UMHPI Controller USER MANUAL UMHPI on board electronic user controller ...
Страница 2: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ...FAE0FA000BZ 00 06 2018 bit ly rdzwebsite ...