UMHPI
Industrial inverter air/water heat pumps with axial fans
32
H10
Enabling of DHW production
/
0
0÷6
INSTALLER
H19
ST8 input configuration
/
0
0÷49
INSTALLER
0 = input not assigned
6 = DHW temperature
ADI2-ADI2
terminals
Serviceable input in
exclusion of D.I.7
H39
Configuration of digital input 2
DI2
/ 2
0÷30
INSTALLER
0 = digital input not assigned
2 = Remote On / Off
DI2/ DI2 terminals
H40
Configurazione DI3
/
3
0÷30
INSTALLATORE
0 = ingresso non assegnato
3 = cambio modo estate / inverno
DI3- DI3 terminals
For activation put H76=1
H44
DI7 configuration
/
0
0÷30
INSTALLER
0 = input not assigned
28 = actuation of DHW thermoregulation from
digital input
ADI2-ADI2 terminals
Serviceable input in
exclusion of ST8.
H54 must be set also.
H54
Polarità ingressi digitali
/
0
0÷255
INSTALLATORE
0 = polarità ingressi digitali=NO
64 = polarità DI7=NC (per chiamata
termoregolatore sanitario da digitale da ADI2-
ADI2).
(2)
H58
Configuration of open
collector 1
/ 24
0÷44
INSTALLER
0 = input not assigned
6 = DHW 3 way valve
21 = Defrosting notification
24 = Alarm notification
31 = Plant season notification
DO3N-DO3 terminals
H61
Configuration of open
collector 1
/ 6
0÷44
INSTALLER
0 = input not assigned
6 = DHW 3-way valve
21 = Defrosting notification
24 = Alarm notification
31 = Plant season notification
NC1, N1, NO1 terminals
H54
Digital input polarity
/
0
0÷255
INSTALLER
0 = digital inputs polarity=NO
64 = polarity DI7=NC (for actuation of DHW
thermo-regulator from the digital input ADI2- ADI2
terminals)
H61
Open collector 1
configuration
/ 6
0÷44
INSTALLER
0 = input not assigned
6 = DHW 3-way valve
Output under 230Vac,
50Hz, 5A resistive, 1A
inductive.
Terminals of exchange
contact NC1, N1, NO1.
It is recommended to
implement
an
external
relay
H76
Remote operating mode
selection (summer/winter)
/ 0 0÷1
INSTALLER
0 = deactivated function
1 = enabled function
H79
Serial address
/
1
1÷200
INSTALLER
In case of several units installed in cascade
configuration, you have to assign different
addresses for each controller.
H82
Enabling of double setpoint
/
0
0÷4
INSTALLER
0 = Selection menu appears on CRH
1= Classic mode
2= Summer double setpoint
3= Winter double setpoint
4 = Summer and winter double setpoint
H83
Enabling of heating always to
divert
towards
the DHW
mode
/ 0 0÷1
INSTALLER
0 = deactivated function
1 = In heating operation always diverts towards the
DHW
(1)
Selectable only for the versions size 125
(2)
Selectable only for the size 125
11.3
ALARMS CONFIGURATION PARAMETERS
Parameter
Description
Unit
Default
Range
Visibility
Allowed configurations
Notes
A08
Antifreeze alarm activation setting
°C 2
-127÷127
INSTALLER
A09
Antifreeze alarm hysteresis
°C
3.0
0.0÷25.5
INSTALLER
A16
Low pressure set in cooling
operation
Bar
according to
the model
4,0÷80,0 INSTALLER
A27
Low pressure set in heating
operation
/ 1.0
0.0÷25.5
INSTALLER