UMHPI
Industrial inverter air/water heat pumps with axial fans
38
12.12
POWER FAILURE
After power supply reset:
•
The system comes back to the previous state before the power failure.
•
If the system is in defrosting period, this mode will be cancelled after power supply reset.
•
All the running timings will be cleared and reset again.
12.13
USER BLOCK ALLARMS TABLE
In the case of indoor/outdoor unit alarm, an error code will appear on the
display of CB
outdoor unit controller
.
Error code
Error description
Compressor
Circulator
Fan motor
E-heaters
E00 Remote
Off OFF
OFF
OFF OFF
E01 High
pressure
OFF
OFF
E02 Low
pressure
OFF
OFF
E05 Antifreeze
alarm
OFF
ON
OFF
ON
E06
Flowswitch / AC fan motor
OFF
OFF
OFF
OFF
E08
Compressors shut off for lack of lubrication
OFF
E18 High
temperature
OFF
OFF
E101
modbus1 connection error [Indoor/outdoor unit]
OFF
OFF
OFF
E611
Input water sensor error
OFF
OFF
OFF
OFF
E612
Plant circuit remote sensor (if enabled)
OFF
OFF
OFF
OFF
E621
Outlet water temperature
OFF
OFF
OFF
OFF
E631
Compressor return sensor
OFF
OFF
OFF
OFF
E641
Compressor exhaust High pressure switch
OFF
OFF
OFF
OFF
E651
High pressure transducer
OFF
OFF
OFF
OFF
E652
Injection high pressure transducer (for “LT” version)
OFF
OFF
OFF
OFF
E661
Low pressure transducer
OFF
OFF
OFF
OFF
E671
Outside air temp. sensor for climatic regulation
OFF
OFF
OFF
OFF
E672
Vapor injection temp. sensor (for “LT” version)
OFF
OFF
OFF
OFF
E681
DHW boiler temp. sensor (if enabled)
OFF
OFF
OFF
OFF
E801
Timeout inverter 1
OFF
OFF
E802
Timeout inverter 2
OFF
OFF
E851
In
verter 1 hardware malfunction
OFF
OFF
E852
In
verter 2 hardware malfunction
OFF
OFF
E861
Compressor 1 overcurrent protection
OFF
OFF
E862
Compressor 2 overcurrent protection
OFF
OFF
E871
Dissipater(heat sink) of Inverter 1 in high temperature
OFF
OFF
E872
Dissipater(heat sink) of Inverter 2 in high temperature
OFF
OFF
E881
Power voltage inverter 1 out of limit
OFF
OFF
E882
Power voltage inverter 2 out of limit
OFF
OFF
*E891
Compressor 1 disconnected from the power supply
OFF
OFF
*E892
Compressor 2 disconnected from the power supply
OFF
OFF
*E901
Compressor 1 model
OFF
OFF
*E902
Compressor 2 model
OFF
OFF
*E911
Inverter 1 overload protection
OFF
OFF
*E912
Inverter 2 overload protection
OFF
OFF
*E921
Inverter 1 overcurrent
OFF
OFF
*E922
Inverter 2 overcurrent
OFF
OFF
*E931
Inverter 1 communication error
OFF
OFF
*E932
Inverter 2 communication error
OFF
OFF
*E941
Inverter 1 PFC
OFF
OFF
*E942
Inverter 2 PFC
OFF
OFF
*E951
Inverter 1 temp. sensor error
OFF
OFF
*E952
Inverter 2 temp. sensor error
OFF
OFF
*E961
Inverter 1 failure
OFF
OFF
*E962
Inverter 2 failure
OFF
OFF
*E971
Inverter 1 EEPROM error
OFF
OFF
*E971
Inverter 2 EEPROM error
OFF
OFF
(*) Only for the models “UMHPI 60”
Содержание UMHPI
Страница 1: ...Chiller and Heat Pumps UMHPI Controller USER MANUAL UMHPI on board electronic user controller ...
Страница 2: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ...FAE0FA000BZ 00 06 2018 bit ly rdzwebsite ...