UMHPI
Industrial inverter air/water heat pumps with axial fans
31
10
AVAILABLE FUNCTIONS WITH EVO TOUCH CONTROLLER (OPTIONAL)
The Evo Touch is a touch screen remote control panel for centralized management of chiller/heat pump, it equipped with humidity
and temperature sensors for environment analysis and for the management of the double setpoint for radiant floor systems
equipped a dehumidification system.
This remote control panel is an intuitive interface very simple for utilization; the functions are all easy to set through the use of
synoptic of immediate understanding.
The functions accessible through the touch screen Control Panel are listed below:
•
Remote management
•
Management of a network, up to 7 heat pumps;
•
Zone thermostat
•
Screed function;
•
Legionella disinfection;
•
Double set-point and dehumidification;
•
Dew point control
•
Climatic compensation
•
Relaunching circulator Management
•
Management of a unique network pump
•
Faults diagnostic system
For further information, please see the user’s-installer’s manual, or contact our offices.
11
TABLE OF ALLOWED PARAMETERS FOR THE USER AND INSTALLER
The parameters can be activated and/or modified by the user or by getting access to the menu of the
CB controller
(using the
installer’s password) located on the front panel of the unit.
DESCRIPTION GROUP
IDENTIFICATIVE CODE
PARAMETER INDEX
VISIBILITY
Configuration CnF
H-
USER/INSTALLER
Compressor CP
C-
INSTALLER
Fan FAn
F-
INSTALLER
Alarms ALL
A-
INSTALLER
Regulation Re
b-
INSTALLER
Pump PUP
P-
INSTALLER
Electric heaters
Fro
r-
INSTALLER
Defrosting dFr
d-
INSTALLER
Electronic valve
EEu
U-
INSTALLER
Offset OFF
o-
INSTALLER
**Mixing valve
rAd
i-
INSTALLER
*Vapor injection
Eiv
u-
INSTALLER
Inverter compressors
nCP
n-
INSTALLER
**Solar SUn
S-
INSTALLER
**DHW preparer
AcS
Ac-
USER/INSTALLER
(*) Parameters present in the UMHPI V series
(**) Parameters present with the optional KIE module.
11.1
SETPOINT CONFIGURATION PARAMETERS
Parameter
Description
Unit
Default
Range
Visibility
Admitted configuration
Notes
Coo
First setpoint in cooling mode
°C
7.0
H03÷Co2
USER
Hea
First setpoint in heating mode
°C
45.0
He2÷H01
USER
San
DHW temperature Setpoint
°C
48.0
H02÷H01
USER
Co2
Second setpoint in cooling mode
°C
18.0
Coo÷H03
USER
He2
Second setpoint in heating mode
°C
35.0
H02÷Hea
USER
rCO
Mixing valve Setpoint in
summer mode
°C 15.0
-50.0÷80.0 USER
Settable if the optional KIE
module is present
rHE
Mixing valvle Setpoint in winter
mode
°C 30.0
-50.0÷80.0 USER
Settable if the optional KIE
module is present
ACS
Setpoint for the instantaneous
domestic hot water production
°C 0.0 0.0÷80.0 USER
Settable if the optional KIE
module is present
11.2
CONFIGURATION PARAMETERS
Parameter
Description
Unit
Default
Range
Visibility
Allowed configurations
Notes
H01
Max setpoint in heating mode
°C (
1)
58.0 -50.0÷80.0
INSTALLER
H02
Min setpoint in heating mode
°C 25.0
-50.0÷80.0
INSTALLER
H03
Max setpoint in cooling mode
°C 23.0
-50.0÷80.0
INSTALLER
H04
Min setpoint in cooling mode
°C 3.0
-50.0÷80.0
INSTALLER
Содержание UMHPI
Страница 1: ...Chiller and Heat Pumps UMHPI Controller USER MANUAL UMHPI on board electronic user controller ...
Страница 2: ......
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ...FAE0FA000BZ 00 06 2018 bit ly rdzwebsite ...