UMHPI
Industrial inverter air/water heat pumps with axial fans
33
11.4
ADJUSTMENT PARAMETERS
Parameter
Description
Unit
Default
Range
Visibility
Allowed configurations
Notes
b01
Band in cooling mode
°C
2,0
0÷10,0
INSTALLER
b02
Band in heating mode
°C
2,0
0÷10,0
INSTALLER
b03
Differential in DHW mode
°C
2,0
0÷10,0
INSTALLER
b04
Commutation time valve radiant
panels
sec 30 0÷600 INSTALLER
b05
Hysteresis cut-off of the
compressor in cooling and heating
°C 1 0.0÷25.5
INSTALLER
Recommended values included between 1 and 1.5
Other different values can ensure the proper
operation of the unit
b06
DHW transitory output in heating
sec
45
0÷255
INSTALLER
b07
Regulator-integral time PI sec
150
0÷255
INSTALLER
A value of 60 sec is recommended for plants with
limited water flow, while for plants with a high
water flow rate a value of 180 sec is recommended.
Other different values may ensure the proper
operation of the unit.
b08
Enabling dynamic set
/
0
0÷1
INSTALLER
b09
Max Offset in cooling dynamic set
°C
3.0
-50.0÷80.0
INSTALLER
b10
Max Offset in heating dynamic set
°C
-3.0
-50.0÷80.0
INSTALLER
b11
Outdoor set temperature in
cooling dynamic set
°C 25
-127÷127
INSTALLER
b12
Outdoor set temperature in
heating dynamic set
°C 15
-127÷127
INSTALLER
b13
Temperature differential in
cooling
°C -10.0
-50.0÷80.0 INSTALLER
b14
Temperature differential in
heating
°C 10.0
-50.0÷80.0
INSTALLER
b15
Setpoint regulation band from
analog input 0-10V
°C 5.0 0.0÷10.0 INSTALLER
b16
Scan time of compressors start-
up
sec 60 0÷255 INSTALLER
b19
Duration of the modulating comp.
at minimum capacity that is
necessary for second comp. startup
sec 30 0÷255 INSTALLER
b20
Enabling of
0-10V/ratiometric input
/ 0 0÷1 INSTALLER
0 = 0-10V input
1 = ratiometric input
b22
Thermoregulation Hysteresis cut-
off plant sensor
°C 1,5 0.0÷25.5 INSTALLER
11.5
CONDENSTATION PARAMETERS
Parameter
Description
Unit
Default
Range
Visibility
Allowed configurations
Notes
F05
Operation under compressor
call
/ 0 0
÷1
INSTALLER
F06
Min fan speed
%
30
0 ÷100
INSTALLER
F07
Max silent fan speed in cooling
mode
%
according to
the model
0 ÷100
INSTALLER
F08
Set of the pressure at the
minimum speed of the fan in
cooling mode
Bar 16.0 -50.0÷80.0
INSTALLER
F09
Proportional band for
modulation of the fan in cooling
mode
Bar 9 0.0÷25.5
INSTALLER
F10
Delta cut-off fan adjustment
Bar
2.6
0.0÷25.5
INSTALLER
F11
Hysteresis cut-off
Bar
1.3
0.0÷25.5
INSTALLER
F13
Max fan speed in cooling mode
%
according to
the model
0 ÷100
INSTALLER
F14
Setting of the pressure at the
maximum fan speed in cooling
mode
Bar 28 -50.0÷80.0
INSTALLER
F15
Min fan speed in heating
%
according to
the model
0 ÷100
INSTALLER
F16
Max. silent fan speed in heating
mode
%
according to
the model
0 ÷100
INSTALLER
F17
Set of the pressure at the
minimum fan speed in heating
mode
Bar 15.0 -50.0÷80.0
INSTALLER
F18
Linear band for fan motor
modulation in heating mode
Bar 7.0 0.0÷25.5
INSTALLER
F19
Max. fan speed in heating mode
%
according to
the model
0 ÷100
INSTALLER
F20
Setting of the pressure at the
maximum fan speed in heating
mode
Bar 6.8 -50.0÷80.0
INSTALLER