UMHPI
Industrial inverter air/water heat pumps with axial fans
17
7.8
ALARM NOTIFICATION
You can configure a digital output for alarm notification function.
In order to enable such function, you should enter into the parameters as following: press PRG
PSS
PRG
(then insert the
service password)
PRG
PAr
PRG
CnF
See paragraph 11.2.
Parameter Unit
Value
Description
Terminals
Notes
*H61
num 24
Undervoltage output
for alarm notification
NO1(Phase)
N1(Neutral)
Undervoltage output 230V ac, 50Hz, 5A resistive, 1A inductive.
Should be connected to the relay coil in order to get a free contact.
(*) Alternatively, it is possible to use another output
DO
or
OC
, see paragraph 6.5.
7.9
SUMMER/WINTER OPERATION NOTIFICATION FUNCTION
It is possible to configure a digital output for the notification of the operating mode of the unit, plant side.
The digital output is active during summer operation, while is not active during heating operation or when the unit is OFF.
During the DHW production and the defrosting, the output maintains the setting of the former season.
For enabling this function, you should enter into the parameters as following: press
PRG
PSS
PRG
(then insert the service
password)
PRG
PAr
PRG
CnF:
See paragraph 11.2.
Parameter Unit
Value
Description
Terminals
Notes
*H61
num 31
Undervoltage output for
plant season notification.
NO1(phase)
N1(neutral)
Undervoltage output 230V ac, 50Hz, 5A resistive, 1A inductive.
Should be connected to the relay coil in order to get a free contact.
(*) Alternatively, it is possible to use another output
DO
or
OC
, see paragraph 6.5.
7.10
COMPRESSOR CRANCKASE HEATER
The crankcase heater operates when the compressor remains off for at least 30 minutes and if the discharge temperature is below
20°C (with hysteresis of 2.0°C). When the compressor restarts, the crankcase heater will stop.
7.11
ANTIFREEZE PROTECTION ELECTRIC HEATERS (IF THE KA ACCESSORY IS PRESENT)
The electric heaters of water antifreeze, installed on the outer surfaces of the evaporator plates, activates even when the unit is
switched off (but energized) if the outlet water temperature goes below
r02
°C (default is 4°C) in heating mode or below
r03
°C
(default is 4°C) in cooling mode and in shut off condition. The same electric heaters are switched off when the temperature
measured by the outlet water sensor exceeds
r02+r06
in heating mode or
r03+r06
in cooling mode and in shut off condition (the
default value is r06=2,0°C). The heating cable placed on the basement of the appliance turns on when the outdoor air temperature
decreases below 3°C and the unit starts the defrosting cycle (or if
r19
=0 even if the unit is not in defrosting cycle, or in stand-by
mode). It will be deactivated if the outdoor temperature exceeds 5°C or the last defrosting cycle is concluded after more than r19
minutes (default 10 minutes) (with
r19
≠
0).
In case you want to produce gelid water, it is necessary to modify the actions of antifreeze resistances, as well as the set of
activation of the antifreeze alarm (
A08 =
4°C by default) and its hysteresis (
A09 =
3.0°C by default).
7.12
ACTIVATION OF DOMESTIC HOT WATER PRODUCTION
To activate the DHW water production mode, be sure to install a temperature sensor inside the tank and to connect it to the
AID2
– AID2
terminals (enabled as analog input). Once the temperature sensor is installed and connected, it is necessary to set the
domestic heat water function.
To enable this function you should get access to the parameters PRG
PSS
PRG
(insert the service password)
PRG
PAr
PRG
CnF
See paragraph 11.2.
I/O Ports - Parameter
Value
Function
H10
0 (default) Disenabled function
1
Function is active in
heating and cooling mode
.
The remote on-off function
doesn’t disenable
the DHW production.
2
Function is active in
heating and cooling mode
.
The remote on-off function
disenables
the DHW production.
*H19
6
Enablement of the DHW temperature sensor.
*H61
(active by default
OC1
)
6
DHW valve command
(*) Alternatively, it is possible to use another I/O ports, see paragraph 6.5.