22
6.1.1
RS485 - X102 Interface
Application:
The serial interface enables the connection of external data loggers or meters.
Select the appropriate RS485 operation mode in the APP configuration:
Connection data logger
→ “Modbus Slave“
Connection meter
→ “Modbus Master“
Wiring:
The number of inverters that can be connected to a joint data logger is limited. Refer to the
data logger manual for details and specifications.
Fig. 6-3 Connection of data logger
6.1.2
Multifunction relay X100 Interface
Application:
The multifunction relay can be configured in two ways:
I.1.1
As an alarm relay. In the event of an inverter fault, the alarm signal is connected.
I.1.2
As a load relay. It will be connected above a defined threshold power generated by the inverter and can be used,
for example, to control a contactor with an external power supply connecting a household consumer.
Wiring:
A number of signals can be operated in parallel as long as the maximum current of 1 A and
24 V is not exceeded.
Fig. 6-4 Connection - Contactor and switchable load