11
5
Electrical Installation
5.1
Connections overview
Fig. 5-1 Overview of wiring area and interior connecting components
Pos
Description
Comment
a
Battery connection area
Battery connectors, Connector Plug Type : Weidmüller WM4
b
RJ45-CAN bus communication
connectors
RJ45-sockets for CAN-bus connection with batteries, Power Sensor
and Power Switch
c
DC load break switch
Normal operation: Switch is in position "1", Turning switch to
position "0" shuts down the inverter when power circuit to battery
is interupted.
d
DC connectors
Two separate solar generator inputs (A & B), Connector type:
Weidmüller WM4.
e
LAN-RJ45
RJ45- socket for connection to router (LAN)
f
Connection area additional
communication
Cable entry for the communication connections on the I/O-curcuit
board (see sections 5.1 to 5.4)
g
AC cable gland
AC-connection cable entry
A
AC terminal block
AC terminal block with terminals for connecting phases L1, L2, L3,
as well as N and PE.
B
Terminals for DC parallel
connection
Terminals for internal wiring of the DC parallel connection of the PV
inputs (see section 5.3).
C
Communication circuit board
The communication circuit board has a serial RS485 interface, a
multifunction relay, 4 digital inputs for ripple control signals and
further digital inputs and outputs (S0) to connect current sensors or
displays.
5.2
AC connection
Procedure: