110
AFI_300mA
current.
Inverter stops feeding.
IDC
IDC_SLOW
Your power storage continually monitors
the quality of current fed in.
If an increased DC-component in AC-
current is detected, inverter stops feeding.
Restart the Power Storage.
If the error still occurs, please contact
service.
CAN_TIMEOUT
CAN communication timeout with battery.
Restart the power storage and reestab-
lish the CAN connection.
RELAYS TEST
Before connection to grid, your power
storage checks the operation of mains
relays. An error was detected during this
check.
Restart the Power Storage
If the error still occurs, please contact
service.
EXT_OFF
Your power storage has the possibility to
be switched off by a configurable “emer-
gency stop”. This signal is active and in-
verter stops feeding.
Check “emergency stop” switch to be
unlocked.
Check configuration of “emergency
stop” function in APP.
RS485_POWER_SW
Error by RS485 communication with the
Power Switch.
Check the RS485 connector fitting.
Check the RS485 connector wire ring .
If the error still occurs, please contact
service.
TEMP_SINK1
Your power storage is designed to feed full
power up to an ambient temperature of
+40°C.
If heatsink temperatures exceed a specific
threshold inverter reduces power.
Check ambient temperature of installa-
tion, clean the heatsink of inverter.
Observe the installation distances spec-
ified in manual.
Remove possible objects laying on the
convection paths of heatsink.
TEMP_HIGH
Your power storage is designed to feed full
power up to an ambient temperature of
+40°C.
If heatsink temperature exceeds a specific
threshold inverter stops feeding.
After the heatsink temperature drops,
inverter restarts feeding.
Check ambient temperature of installa-
tion.
Clean the heatsink of inverter.
Observe the installation distances spec-
ified in manual.
Remove possible objects laying on the
convection paths of heatsink.
TEMP_BAT
Your power storage is designed to feed full
power up to an ambient temperature of
+40°C.
The charge/discharge current will be re-
duced.
If heatsink temperature exceeds the bat-
tery will be disconnected.
Check ambient temperature of installa-
tion.
Clean the heatsink of inverter.
Observe the installation distances spec-
ified in manual.
Remove possible objects laying on the
convection paths of heatsink.