98
8.5.3.4
Firmware update over network connection
The network connection of Master and Slave devices allows for an update of the Control Software for the Master device
followed by a subsequent software update of the Slaves devices. This function deactivated by default and requires activation
in the RCT Power APP.
Unfortunately, an update of the BMS software over a network is not possible at the moment.
Please note that when you update the software over the network, the master unit must always be
updated first. Otherwise, the system may be affected by unforeseeable issues.
Step
Description
1
Launch “RCT Power APP“ and
establish a connection to your
Master device.
2
Press the settings icon “
“.
3
Tap on "LOGIN" Enter the password in the dialogue box and
press “OK“ to enter the configuration options screen.
(Login Customer Area, password:
“********“)
Please use the installer password to login as an installer.
4
Go to "DEVICE"-
→ "Settings"
-
→ "Update".
Under "Control Update" set tick mark for
"Activate aut. update slaves".
5
Please confirm the changed parameter with "Yes" in the
dialogue box. An update of the Master device Control Software
will automatically update the Control Software of all connected
Slave device.
If the master device has a more current software version than one of the slaves before the activation of
the automatic update parameter, the update process starts immediately. Changed settings cannot be
stored. Only one slave at a time can be updated.