16
GB
Connecting a potential-free roller shutter switch with + 12 V.
pink (6)
12 V
Control input
A
white (3)
B
yellow (4)
Potential-free closer
contact of a roller shutter
switch
(example)
Setting mode in menu and : (when both inputs are in use)
Control input
A
(open)
Control input
B
(close)
Switching signals:
OPEN (opening) or CLOSE (closing)
NOTE
◆
Dead-man operation
The drive moves the door in the corresponding direction for as long as the signal persists. If
the signal lapses during travel the drive stops.
◆
Control inputs
A
and
B
must not both be set to mode and . If the required
application can be implemented using only one control input, the second control input can be
set to any other function.
Further applications:
◆
Automatic operation with the aid of a thermostat.
For this function a thermostat must be connected via a changeover contact.
◆
Automatic operation with the aid of a timer control (e.g. a 230 V roller
shutter control).
For this function the roller shutter control must be connected using a cut-off relay.
CAUTION
The cut-off relay must maintain the necessary safety barrier between the 230 V mains and
the low-voltage side.
Connecting a roller shutter switch