
QUANTECH
39
Form QCC2-NM1
Issue Date: 5/20/2021
5
Operational limits (English)
Voltage limitations
The following voltage limitations are absolute and
operation beyond these limitations may cause serious
damage to the compressor.
Table 5 -
Voltage Limitations
UNIT POWER
MIN.
MAX.
200-3-60
180
220
230-3-60
207
253
380/415-3-60
342
440
460-3-60
414
506
380/415-3-50
342
440
575-3-60
517
633
Section 5 – Technical data
Notes:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest Quantech Sales Representative for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest Quantech Sales Representative for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
3. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed
4. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
Excessive flow will cause damage to the
cooler. Do not exceed max. cooler flow.
Special care should be taken when mul-
tiple chillers are fed by a single pump.
Содержание QCC2015CEE
Страница 12: ...QUANTECH 12 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 38: ...QUANTECH 38 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 46: ...QUANTECH 46 Form QCC2 NM1 Issue Date 5 20 2021 Section 5 Technical data THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 102: ...QUANTECH 102 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 152: ...QUANTECH 152 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 171: ...QUANTECH 171 Form QCC2 NM1 Issue Date 5 20 2021 Notes...