QUANTECH
140
Form QCC2-NM1
Issue Date: 5/20/2021
SECTION 8 – UNIT OPERATION
BAS/EMS discharge air temperature reset using
a voltage or current signal
The Remote Reset Option allows the Control Center
of the unit to reset the discharge air temperature set-
point using a 0 VDC to 10 VDC input, or a 4 mA to
20 mA input connected to XTBC1 terminals A- and
A+. Whenever a reset is called for, the change may be
noted by pressing the COOLING SETPOINTS key
twice. The new value will be displayed as “REM SETP
= XXX°F.”
If a 0 - 10 VDC signal is supplied, it is applied to termi-
nals A+ and A-, and jumper JP1 on the I/O board must
be inserted between pins 2 and 3. To calculate the reset
discharge air temperature setpoint for values between
0VDC and 10VDC use the following formula:
Setpoint = Local Discharge Air Temp Se °Reset
°Reset = (DC voltage signal) x (*Max Reset Value)
10
Example:
Local Discharge Air Temp Setpoint = 45°F (7.22°C)
*Max Reset Value = 20°F (11.11°C)
Input Signal = 6VDC
(English)
°Reset = 6VDC x 20°F = 12°F Reset
10
New Setpoint = 45°F + 12°F = 57°F
(Metric)
°Reset = 6VDC x 11. 11°C = 6.67°C Reset
10
New Setpoint = 7.22°C + 6.67°C = 13.89°C
* Max Reset Value is the “Max EMS-PWM Remote Temp. Reset” set-
point value described in the programming section under Cooling
Setpoints. Programmable values are from 2°F to 40°F (1.11°C to
11.11°C).
**NOTE:
The Suction Pressure Setpoints are not remotely
resettable.
If a
4‑20mA signal is supplied,
it is applied to termi-
nals A+ and A- and
jumper JP1 on the I/O board
must be installed between pin 1 and 2
. To calculate
the discharge air temperature setpoint for values be-
tween 4 mA and 20 mA use the following formula:
Setpoint = Local Discharge Air Temp Se °Reset
°Reset = (mA signal - 4) x (*Max Reset Value)
16
Example:
Local Discharge Air Temp Setpoint = 45° (7.22°C)
*Max Reset Value = 10°F (5.56°C)
Input Signal = 12mA
(English)
°Reset = 8mA x 10°F = 5°F Reset
16
Setpoint = 45°F + 5°F = 50°F
(Metric)
°Reset = 8mA x 5.56°C = 2.78°C Reset
16
Setpoint = 7.22°C + 2.78°C = 10.0°C
A 240-24 Volt Ratio Transformer (T3) is
used to derive nominal 12 volt output from
the 120 volt supply.
Содержание QCC2015CEE
Страница 12: ...QUANTECH 12 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 38: ...QUANTECH 38 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 46: ...QUANTECH 46 Form QCC2 NM1 Issue Date 5 20 2021 Section 5 Technical data THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 102: ...QUANTECH 102 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 152: ...QUANTECH 152 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 171: ...QUANTECH 171 Form QCC2 NM1 Issue Date 5 20 2021 Notes...