QUANTECH
29
Form QCC2-NM1
Issue Date: 5/20/2021
4
To ensure warranty coverage, this equip-
ment must be commissioned and serviced
by an authorized Quantech service
mechanic or a qualified service person
experienced in equipment installation. In-
stallation must comply with all applicable
codes, particularly in regard to electrical
wiring and other safety elements such as
relief valves, HP cutout settings, design
working pressures, and ventilation re-
quirements consistent with the amount
and type of refrigerant charge.
Lethal voltages exist within the control
panels. Before servicing, open and lock-
out/tagout all disconnect switches.
Installation checklist
The following items, 1 through 5, must be checked be-
fore placing the units in operation.
1. Inspect the unit for shipping damage.
2. Rig unit using spreader bars.
3. Open the unit only to install water piping sys-
tem. Do not remove protective covers from water
connections until piping is ready for attachment.
Check water piping to ensure cleanliness.
4. Pipe unit using good piping practice
(see ASHRAE
handbook section 215 and 195).
5. Check to see that the unit is installed and operated
within limitations
(Refer to Limitations).
The following pages outline detailed procedures to be
followed to install and start-up the unit.
Handling
These units are shipped as completely assembled units
containing full operating charge, and care should be
taken to avoid damage due to rough handling.
Location and clearances
These units are designed for outdoor installations on
ground level, rooftop, or beside a building. Location
should be selected for minimum sun exposure and to
ensure adequate supply of fresh air for the condenser.
The units must be installed with sufficient clearances
for air entrance to the condenser coil, for air discharge
away from the condenser, and for servicing access.
Section 4 – Installation
In installations where winter operation is intended and
snow accumulations are expected, additional height
must be provided to ensure normal condenser air flow.
Clearances are listed in
Foundation
The unit should be mounted on a flat and level foun-
dation, floor, or rooftop capable of supporting the en-
tire operating weight of the equipment.
for operating weight
.
If the unit is elevated
beyond the normal reach of service personnel, a suit-
able catwalk must be capable of supporting service
personnel, their equipment, and the compressors.
Ground level locations
It is important that the units be installed on a sub-
stantial base that will not settle. A one piece concrete
slab with footers extended below the frost line is
highly recommended. Additionally, the slab should
not be tied to the main building foundations as noise
and vibration may be transmitted. Mounting holes are
provided in the steel channel for bolting the unit to its
foundation. See
For ground level installations, precautions should be
taken to protect the unit from tampering by or injury to
unauthorized persons. Screws and/or latches on access
panels will prevent casual tampering. However, further
safety precautions such as a fenced-in enclosure or
locking devices on the panels may be advisable.
Rooftop locations
Choose a spot with adequate structural strength to
safely support the entire weight of the unit and service
personnel. Care must be taken not to damage the roof.
Consult the building contractor or architect if the roof is
bonded. Roof installations should have wooden beams
(treated to reduce deterioration), cork, rubber, or vibra-
tion isolators under the base to minimize vibration.
Noise sensitive locations
Efforts should be made to ensure that the unit is not
located next to occupied spaces or noise sensitive areas
where unit noise level would be a problem. Unit noise
is a result of compressor and fan operation. Consider-
ations should be made using noise levels published in
the Quantech Engineering Guide for the specific con-
densing unit model. Sound blankets for the compres-
sors and low sound fans are available.
Содержание QCC2015CEE
Страница 12: ...QUANTECH 12 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 38: ...QUANTECH 38 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 46: ...QUANTECH 46 Form QCC2 NM1 Issue Date 5 20 2021 Section 5 Technical data THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 102: ...QUANTECH 102 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 152: ...QUANTECH 152 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 171: ...QUANTECH 171 Form QCC2 NM1 Issue Date 5 20 2021 Notes...