SECTION 9 – SERVICE AND TROUBLESHOOTING
Service mode – condensing unit
configuration
After the Outputs are displayed, the next group of dis-
plays relate to unit configuration and start/hour coun-
ters. Data logging, soft start, refrigerant type, pump
control selection, and expansion valve type all must be
programmed to match the actual unit configuration.
Soft start (disabled), Refrigerant Type
(R410A), and Expansion Valve Type
(Thermostatic), and North American
Feature (Enabled) MUST be correctly
programmed or damage to compressors
and other system components may result.
The following is a list of unit configuration selections,
in order of appearance:
HOT GAS BYPASS TYPE
UNIT TYPE (STANDARD OR HEAT PUMP)
COMPRESSOR HOURS
COMPRESSOR STARTS
DATA LOGGING TIMER X SECS
FAN CONTROL TYPE (SINGLE)
SOFT START (DISABLED)
REFRIGERANT TYPE (R410A ONLY)
EXPANSION VALVE TYPE (THERMOSTATIC
ONLY)
REMOTE TEMP RESET OPTION =
REMOTE INPUT SERVICE TIME =
“NORTH AMERICAN FEATURE SET ENABLED”
HYDRO PUMP SELECTION
EVAP PUMP TOTAL RUN HOURS
SYS 1 HOURS
SYS 2 HOURS
SYS 1 STARTS
SYS 2 STARTS
The last displays shown on the above list are for the
accumulated run and start timers for each system. All
values can also be changed using the ↑ (UP) and ↓
(DOWN) arrow keys, but under normal circumstances
would not be required or advised. After the last start
display, the microboard will display the first program-
mable value under the PROGRAM key.
Service mode – analog and digital inputs
After entering Service Mode (PROGRAM
↑↑ ↓↓)
,
all digital and analog inputs to the microboard can be
viewed by pressing the OPER DATA key. After press-
ing the OPER DATA key, the ↑ (UP) arrow and ↓
(DOWN) arrow keys are used to scroll through the
analog and digital inputs.
The following is the order of analog and digital inputs
that will appear when sequenced with the
↓ (
DOWN)
arrow key:
(analog inputs)
SYS 1 SUCT PRESSURE
UNIT TYPE
SYS 1 *DISCH PRESSURE
SYS 1** SUCTION TEMP.
SYS 2** SUCTION TEMP.
AMBIENT AIR TEMP.
LEAVING LIQUID TEMP.
RETURN LIQUID TEMP.
SYS 2 SUCTION PRESSURE
SYS 2 SPARE
SYS 2 *DISCH PRESSURE
SYS 1 MTR VOLTS
SYS 2 MTR VOLTS
(DIGITAL INPUTS)
PWM TEMP RESET INPUT
LOAD LIMIT INPUT
FLOW SW / REM START
SPARE
SINGLE SYSTEM SELECT
SYS 1 MP / HPCO INPUT
SYS 2 MP / HPCO INPUT
* The discharge pressure transducer is optional on some models.
** The suction temperature sensor is on EEV units only.
The analog inputs will display the input connection,
the temperature or pressure, and corresponding input
voltage such as:
S Y S 1 S U C T P R J 7 - 1 0
2 . 1 V D C = 8 1 P S I G
Содержание QCC2015CEE
Страница 12: ...QUANTECH 12 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 38: ...QUANTECH 38 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 46: ...QUANTECH 46 Form QCC2 NM1 Issue Date 5 20 2021 Section 5 Technical data THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 102: ...QUANTECH 102 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 152: ...QUANTECH 152 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 171: ...QUANTECH 171 Form QCC2 NM1 Issue Date 5 20 2021 Notes...