SECTION 7 – UNIT CONTROLS
Form QCC2-NM1
Issue Date: 5/20/2021
7
Display/Print keys
00067VIP
The DISPLAY/PRINT keys allow the user to retrieve
system and unit information that is useful for moni-
toring unit operation, diagnosing potential problems,
troubleshooting, and commissioning the unit.
System and unit information, unit options, setpoints,
and scheduling can also be printed out with the use of
a printer. Both real-time and history information are
available.
Oper Data key
The OPER DATA key gives the user access to unit and
system operating parameters. When the OPER DATA
key is pressed, system parameters will be displayed
and remain on the display until another key is pressed.
After pressing the OPER DATA key, the various op-
erating data screens can be scrolled through by using
the ↑ (UP) and ↓ (DOWN) arrow keys or the ENTER/
ADV key located under the “ENTRY” section.
System 2 information will only be dis-
played for 2 system units.
With the “UNIT TYPE” set as a condensing unit (via
jumper between J11-7 and J11-12 on the I/O Board),
the following list of operating data screens are view-
able under the OPER DATA key in the order that
they are displayed. The
↓
(DOWN) arrow key scrolls
through the displays in the order they appear below:
The unit MUST be set to be a condensing
unit via jumper between J11-7 and J11-12
on the I/O Board. DO NOT operate the
unit if not correctly set up.
D I S C H A R G E A I R T E M P
= 5 7 . 4 ° F
This display shows the discharge air temperature leav-
ing the evaporator. The display will only be shown
when the Control Mode is programmed for Discharge
Air (under the OPTIONS key). The minimum limit on
the display for these parameters are 9.2°F (-12.7°C).
The maximum limit on the display is 85.4°F (29.7°C).
A M B I E N T A I R T E M P
= 8 7 . 5 ° F
This display shows the ambient air temperature. The
minimum limit on the display is 0.4°F (-17.6°C). The
maximum limit on the display is 131.2°F (55.1°C).
Содержание QCC2015CEE
Страница 12: ...QUANTECH 12 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 38: ...QUANTECH 38 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 46: ...QUANTECH 46 Form QCC2 NM1 Issue Date 5 20 2021 Section 5 Technical data THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 102: ...QUANTECH 102 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 152: ...QUANTECH 152 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 171: ...QUANTECH 171 Form QCC2 NM1 Issue Date 5 20 2021 Notes...