A60 Recovery
If your F3200E ever suffers corruption of its stored programs, it may no longer be able to
communication with it via normal means. This could happen if you were to suffer a power
failure or communications interruption during a firmware update. We hope this never happens to
you, but in case it ever does, the A60 recovery utility can recover the situation. We recommend
that you only use this utility under direction of Pyramid.
CAUTION
Do not use the A60 Recovery utility except under the direction of Pyramid. Misuse could render
your F3200E inoperable, and you would then need to return it to the factory for repair.
24.1 Starting the A60 Recovery Utility
You need to start the F3200E in bootloader mode. To invoke this, you must fit a 2mm jumper to
position one of jumper JPR5. JPR5 is located close to the fiber optic mezzanine board near the
rear of the main circuit board.
Disconnect power from the F3200E. The jumper can be accessed by removing the four small
screws at the rear of the top cover of the unit, sliding the cover back and removing it. JPR5 is
located near the rear panel, between the gate BNC connectors and the LED indicators. Make
sure you are well grounded to the F3200E chassis before touching the jumper or any other
internal component, to prevent damaging the electronics by static discharge. Fit the jumper and
ensure all other positions on JPR5 are open.
Figure 76. JPR 5 location; bootloader mode jumper position.