![Pyramid Technical Consultants F3200E Скачать руководство пользователя страница 100](http://html1.mh-extra.com/html/pyramid-technical-consultants/f3200e/f3200e_user-manual_1632602100.webp)
PSI System Controls and Diagnostics
F3200E User Manual
F3200E_UM_180726 Page 100 of 107
security)
Messages being blocked by
anti virus software.
Disable anti-virus software
Set up allowed channels for
F3200E messages.
Unexpected changes to
F3200E state
Another host is
communicating with the
F3200E.
Change IP address.
Use a direct cable connection
instead of a network.
Set up IP addresses and subnet
masks to prevent conflicts.
Communications interruptions Other processes on PC host
interfering with comms ports.
Use a dedicated PC with
simple configuration and
minimum number of processes
running.
Unable to connect on fiber
optics
Using wrong fiber optic
channel
Check connections
Connect on channel 2 if
F3200E is a looped device.
Fiber optic loop topology
incorrect.
Check Tx to Rx links around
the loop.
Correct loop topology.
Bad fiber optic
Check fiber optic light
attenuation.
Replace or repair bad fiber
optic cables.
Loop controller does not
support F3200E
Check loop controller
firmware version
Update firmware.
Unable to connect on serial
port
Another program is using the
COM port.
Try to access the required port
with puTTY or RealTerm.
Choose another port or close
down the other program.
Incorrect port settings.
Check port settings
Correct the settings.
Incorrect cable.
Make up a suitable cable.
F3200E mode switch not set
correctly.
Check setting.
Correct the setting.