Configuring the MVI56-PDPMV1 Module
MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 128 of 251
ProSoft Technology, Inc.
6
Next, expand the tag MVI56PDPMV1.Mailbox.GetLiveList.Station, to verify
that the MVI56-PDPMV1 responded to the GetLiveList message.
For MVI56PDPMV1.Mailbox.GetLiveList.Station[1] (the PROFIBUS Master
Address), notice that the value has changed from 4 (not communicating) to 3
(Master).
For MVI56PDPMV1.Mailbox.GetLiveList.Station[125] (the PROFIBUS Slave
Address configured in the Configuring the PROFIBUS Slaves (page 85)
procedure), notice that the value has changed from 4 (not communicating) to
0 (Slave OK)