Diagnostics and Troubleshooting
MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 180 of 251
ProSoft Technology, Inc.
Scenario
Debug Access After Power Up
LED Behavior After Power Up
LEGACY Ladder loaded to
processor (module is inserted in
configured slot)
Yes
MSTR STAT= GREEN
COM STAT= GREEN or OFF (depends if the
module is communicating with PROFIBUS
slaves)
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = AMBER
APP STATUS= AMBER
FLEX Ladder
Yes
MSTR STAT= GREEN (1sec) /RED (2 secs)
COM STAT= OFF
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = OFF
APP STATUS= AMBER
4.2.5 Flex Mode (Use Legacy Mode=No)
Scenario
Debug Access After Power Up
LED Behavior After Power Up
- Module located in slot that is not
configured
OR
- No processor
OR
- Neither sample logics loaded to
processor (LEGACY or FLEX)
No
(Waiting for connection to
processor)
MSTR STAT= OFF
COM STAT=OFF
DBASE STAT=GREEN
TKN HLD= OFF
OK = RED
BP ACT = AMBER
APP STATUS= AMBER
LEGACY Ladder
Yes
MSTR STAT= RED
COM STAT= OFF
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = OFF
APP STATUS= AMBER
FLEX Ladder
Yes
MSTR STAT= GREEN
COM STAT= GREEN or OFF (depends if
the module is communicating with
PROFIBUS slaves)
DBASE STAT= GREEN
TKN HLD= GREEN
OK = GREEN
BP ACT = AMBER
APP STATUS= OFF
Содержание MVI56-PDPMV1
Страница 1: ...MVI56 PDPMV1 ControlLogix Platform PROFIBUS DPV1 Master August 5 2021 USER MANUAL...
Страница 4: ......
Страница 174: ...MVI56 PDPMV1 ControlLogix Platform User Manual PROFIBUS DPV1 Master Page 174 of 251 ProSoft Technology Inc...
Страница 196: ...MVI56 PDPMV1 ControlLogix Platform User Manual PROFIBUS DPV1 Master Page 196 of 251 ProSoft Technology Inc...
Страница 246: ...MVI56 PDPMV1 ControlLogix Platform User Manual PROFIBUS DPV1 Master Page 246 of 251 ProSoft Technology Inc...