Start Here
MVI56-PDPMV1 ♦ ControlLogix Platform
User Manual
PROFIBUS DPV1 Master
Page 72 of 251
ProSoft Technology, Inc.
Enter the
RPI
time that will provide optimum backplane performance for your
application, within the range from
5
MS
to
750
MS
.
RPI Time 750 milliseconds
If ALL of the following conditions are true:
MVI56-PDPMV1 module firmware version 1.21 (or later)
MVI56-PDPMV1 module configured in FLEX mode (
U
SE
L
EGACY
M
ODE
=
N
O
)
MVI56-PDPMV1 module is located in either the local rack or remote rack
through EtherNet/IP adapters
For optimal performance set the
RPI
time as
750
MS
. For this scenario, the
module will use the
IOT (Immediate Output)
instruction that will override the
configured
RPI
time. Setting a lower
RPI
time will cause unnecessary interrupts
to the module, delaying data updates and lowering data throughput.