ProSoft Technology, Inc.
2.5
Verifying Correct Operation
The final step is to verify that the MVI56-PDPMV1 module is communicating with
the PROFIBUS slave. Choose the method that best suits your connection and
proximity to the modules and the processor.
If you are able to view the module directly: Checking the PROFIBUS LEDs on
the MVI56-PDPMV1 (page 119)
If you are able to connect to the module using ProSoft Configuration Builder
and a serial cable:Viewing the Fieldbus Data from the MVI56-
PDPMV1’s
Configuration/Debug Menu (page 122)
If you are able to connect to the processor using RSLogix 5000: Viewing the
Controller Tags in RSLogix 5000 (page 124)
If you are able to connect to the processor using RSLogix 5000: Sending a
Mailbox Message in RSLogix 5000 (page 127)
2.5.1 Checking the PROFIBUS LEDs on the MVI56-PDPMV1
If all four PROFIBUS LEDs are illuminated green, then the PROFIBUS
Master is communicating and exchanging data with all configured PROFIBUS
slaves.
If the COM STAT LED is green and flashing, the PROFIBUS Master is
communicating and exchanging data with at least one of the configured
slaves.
If the COM STAT LED is red, there is a communication or configuration error.
If the COM STAT LED is off, the PROFIBUS Master is not communicating
with any slaves. The most likely reason is that the slaves are not correctly
configured.
After restarting the MVI56-PDPMV1 Master and the PROFIBUS slave, look at
the PROFIBUS cable connection. If all the PROFIBUS LEDs on the MVI56-
PDPMV1 are illuminated green, then the Master is communicating
successfully with all slaves.
Содержание MVI56-PDPMV1
Страница 1: ...MVI56 PDPMV1 ControlLogix Platform PROFIBUS DPV1 Master August 5 2021 USER MANUAL...
Страница 4: ......
Страница 174: ...MVI56 PDPMV1 ControlLogix Platform User Manual PROFIBUS DPV1 Master Page 174 of 251 ProSoft Technology Inc...
Страница 196: ...MVI56 PDPMV1 ControlLogix Platform User Manual PROFIBUS DPV1 Master Page 196 of 251 ProSoft Technology Inc...
Страница 246: ...MVI56 PDPMV1 ControlLogix Platform User Manual PROFIBUS DPV1 Master Page 246 of 251 ProSoft Technology Inc...