MVI56-PDPMV1 ♦ ControlLogix Platform
Start Here
PROFIBUS DPV1 Master
User Manual
Page 51 of 251
ProSoft Technology, Inc.
5
Click the
C
ONNECTION
tab, and then enter the
Requested Package Interval
(RPI)
value.
o
If the module is located in the local rack (same rack where the processor
is located) or in a remote rack connected through EtherNet/IP adapters,
select the maximum value of
750
MS
.
o
If the module is located in a remote rack connected through ControlNet
adapters, adjust the
RPI
time to be not less than
5
MS
and not less than
(and, preferably, some even multiple of) the RSNetWorx for ControlNet
Network Update Time (NUT).
6
Click
OK
to confirm.
Now the MVI56-PDPMV1 module will be visible in the
I/O Configuration
section.