MVI56-PDPMV1 ♦ ControlLogix Platform
Mailbox Messaging
PROFIBUS DPV1 Master
User Manual
Page 153 of 251
ProSoft Technology, Inc.
Acyclic Message Status Word
Refer to Acyclic Message Status Word (page 170).
Slave Address
Range 1 to 125; specifies the slave from which to read the configuration.
Error Code [1 … 4]
If "Return Code" equals 3080h ("Negative indication from lower layer"), status
values according to the DP-specification may be available in "Error Code 1",
Error Codes 2 through 3 are reserved. Refer toMailbox Messaging Error Codes
(page 170).
Return Code
Refer to Mailbox Messaging Error Codes (page 170).
Fault Information
If "Invalid other" is returned in the Acyclic Message Status Word in the header of
the response, information about the fault can be found here. Refer to Acyclic
Message Status Word (page 170).
0100h:
Address out of range.
0A00h
: Failed to execute request. Refer to Return Codes (page 171) for
additional information.
0B00h
: Remote station failure. Refer to Return Codes (page 171) for additional
information.
FF00h
: Module not initialized.
Identifier Bytes [1 … n]
Refer to EN50170 Vol. 2 for information on the structure of these bytes. In
addition, refer to the documentation provided with the slave device for more
information.
Содержание MVI56-PDPMV1
Страница 1: ...MVI56 PDPMV1 ControlLogix Platform PROFIBUS DPV1 Master August 5 2021 USER MANUAL...
Страница 4: ......
Страница 174: ...MVI56 PDPMV1 ControlLogix Platform User Manual PROFIBUS DPV1 Master Page 174 of 251 ProSoft Technology Inc...
Страница 196: ...MVI56 PDPMV1 ControlLogix Platform User Manual PROFIBUS DPV1 Master Page 196 of 251 ProSoft Technology Inc...
Страница 246: ...MVI56 PDPMV1 ControlLogix Platform User Manual PROFIBUS DPV1 Master Page 246 of 251 ProSoft Technology Inc...