MVI56-PDPMV1 ♦ ControlLogix Platform
Mailbox Messaging
PROFIBUS DPV1 Master
User Manual
Page 165 of 251
ProSoft Technology, Inc.
Conf. Req.
00h:
Confirmation is not required
01h:
Confirmation required. All confirmations are automatically sent by the
Master; the user is not required to send a confirmation message.
Fault Information
If "Invalid Other" is returned in the Message Information word in the header of the
response, information about the fault can be found here. Refer to Return Codes
(page 171) for more information.
0100h:
Invalid operating mode
FF00h
: Module not initialized