DESCRIPTION:
DATE:
DRAWING NO:
6 of 11
SHEET:
REVISION:
B
NOTE:
Callout letter
and
map to drawing #164201409---5
,
,
101503
A
B
C
164201409---1
POWER WIRING INSTALLATION NOTES
A---7
Powerware BPIV Parallel Cabinet Installation and Operation
164201409 REV. B
101503
Table J. INPUT/OUTPUT Ratings & External Wiring Requirements for
Powerware BPIV---30 Parallel Cabinet
(3 + 1 Configuration)
Ratings
Units
Rating 50/60 Hz
Basic unit ratings at
0 7 l
i
PF l d
UPM KVA
30
g
0.7 lagging PF load
INPUT/OUTPUT
VOLTAGE
208
AC Input from UPM
(0 7PF)
Amps
183 3
AC Input from UPM
(0.7PF)
3
(1) N
l (1)
d
Amps
183.3
AC
INPUT
p
(
)
3
, (1) Neutral, (1) gnd
Minimum conductor size (number per
)
AWG or kcmil(ea)
Refer to Powerware BPIV
UPS Installation and
Operation manual for
wire size.
(Input current and wiring size is for each module)
AC
AC Input to Bypass (UPM Bypass)
Full Load Current
3
, (1) Neutral, (1) gnd
Amps
249.9
AC
INPUT
Full Load Current
3
, (1) Neutral, (1) gnd
Minimum conductor size (number per
)
AWG or kcmil(ea)
2/0 (2)
AC
AC Output to Critical Load
Full Load Current 3
(1) Neutral (1) gnd
Amps
249.9
AC
OUTPUT
Full Load Current 3
, (1) Neutral, (1) gnd
Minimum conductor size (number per
)
AWG or kcmil(ea)
2/0 (2)
Содержание BPIV 15 kVA
Страница 1: ...Parallel Cabinet 15 kVA and 30 kVA BPIV INSTALLATION OPERATION MANUAL...
Страница 2: ......
Страница 3: ...www powerware com BPIV INSTALLATION OPERATION MANUAL Parallel Cabinet 15 kVA and 30 kVA...
Страница 15: ...Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV B 101503 Section I Installation...
Страница 31: ...Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV B 101503 Section II Operation...
Страница 102: ...W 2 Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV B 101503 This Page Intentionally Left Blank...
Страница 103: ......
Страница 104: ...164201409 Rev B 164201409B...