vii
Powerware BPIV Parallel Cabinet Installation and Operation
164201409 REV. B
101503
Introduction
The Powerware BPIV Parallel System can be utilized to prevent loss of valuable
electronic information, minimize equipment downtime, and/or minimize the adverse
effect on equipment and production due to unexpected power problems.
The Powerware
BPIV
Parallel System continually monitors incoming electrical power
and removes the surges, spikes, sags, and other irregularities that are inherent in
commercial utility power. Working with the building’s electrical system, the Parallel
System supplies clean, consistent power that sensitive electronic equipment requires
for reliable operation. During brownouts, blackouts, and other power interruptions,
optional batteries provide emergency power to safeguard operation.
The Parallel System allows two to four UPMs to operate in parallel capacity or
redundancy to provide more capacity than a single UPM and as backup for each other.
In addition, when one UPM is taken out of service for maintenance or is not operating
properly, a redundant UPM continues to supply uninterrupted power to the critical load.
The Parallel System refers to the Parallel Cabinet in conjunction with the UPMs. The
Parallel System consists of one Parallel Cabinet, and two or more UPMs. Each UPM
may have its own internal battery, and/or optional battery cabinets.
This manual describes how to install and operate your Powerware BPIV Parallel
System. The installation section contains instructions for installing the Parallel Cabinet
.
The operation section contains instructions for operating the Parallel Cabinet and
UPMs while paralleling for capacity/redundancy. The information you use depends on
the system you purchased.
NOTE:
The installation procedures of this manual only refer to the Parallel Cabinet and its
connection to the UPMs for parallel capacity/redundancy operation. The operation
section of this manual refers to the operation for the Parallel Cabinet and the UPMs
when paralleling for capacity/redundancy. For full installation and operation of the
UPMs, refer to the
Powerware BPIV UPS Installation and Operation
manual
referenced at the end of this section.
Содержание BPIV 15 kVA
Страница 1: ...Parallel Cabinet 15 kVA and 30 kVA BPIV INSTALLATION OPERATION MANUAL...
Страница 2: ......
Страница 3: ...www powerware com BPIV INSTALLATION OPERATION MANUAL Parallel Cabinet 15 kVA and 30 kVA...
Страница 15: ...Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV B 101503 Section I Installation...
Страница 31: ...Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV B 101503 Section II Operation...
Страница 102: ...W 2 Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV B 101503 This Page Intentionally Left Blank...
Страница 103: ......
Страница 104: ...164201409 Rev B 164201409B...