DESCRIPTION:
DATE:
DRAWING NO:
11 of 11
SHEET:
REVISION:
A
061502
164201409---1
POWER WIRING INSTALLATION NOTES
A---12
Powerware BPIV Parallel Cabinet Installation and Operation
164201409 REV. B
101503
16.
Output overcurrent protection and output disconnect switch are to be provided by the
user. Table P lists the maximum rating for output circuit breakers satisfying the criteria for
both.
Table P. Maximum Output Circuit
Breaker Ratings
System Configuration
Output Volt-
age Rating
System Configuration
208VAC
BPIV---15 (1+1)
60A
BPIV---15 (2+0)
110A
BPIV---15 (2+1)
110A
BPIV---15 (3+0)
175A
BPIV---15 (3+1)
175A
BPIV---30 (1+1)
110A
BPIV---30 (2+0)
225A
BPIV---30 (2+1)
225A
BPIV---30 (3+0)
350A
BPIV---30 (3+1)
350A