2--1
Powerware BPIV Parallel Cabinet Installation and Operation
164201409 REV. B
101503
Installing the Parallel System
2.1
Preliminary Installation Information
WARNING:
Installation should be performed only by qualified personnel.
Refer to the following while installing the system:
•
Refer to Appendix A of this manual for installation drawings and additional
installation notes.
•
Dimensions in this manual are in millimeters and inches.
•
Do not tilt the cabinets more than
10
˚
during installation.
•
The conduit landing plates are to be removed to add conduit landing holes as
required. Plate material is 16 gauge steel (0.060 in. thick).
•
The cabinets must be installed on a level floor suitable for computer or
electronic equipment.
•
If perforated floor tiles are required for ventilation, place them in front of the
Parallel System. Refer to Table R in Appendix A for equipment weight and point
loading.
•
Details about control wiring are provided in the Parallel Cabinet installation
procedure. Drawing 164201409---2 and Table Q in Appendix A identify the
control wiring terminations.
2.2
UPM Cabinet Installation
To install the UPMs, refer to the Powerware BPIV UPS Installation and Operation
manual referenced in the Introduction to this manual.
2
Содержание BPIV 15 kVA
Страница 1: ...Parallel Cabinet 15 kVA and 30 kVA BPIV INSTALLATION OPERATION MANUAL...
Страница 2: ......
Страница 3: ...www powerware com BPIV INSTALLATION OPERATION MANUAL Parallel Cabinet 15 kVA and 30 kVA...
Страница 15: ...Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV B 101503 Section I Installation...
Страница 31: ...Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV B 101503 Section II Operation...
Страница 102: ...W 2 Powerware BPIV Parallel Cabinet Installation and Operation 164201409 REV B 101503 This Page Intentionally Left Blank...
Страница 103: ......
Страница 104: ...164201409 Rev B 164201409B...