Important
The function is switched off by the settingOff or automatically if the
maximum boiler temperature is reached.
It can also be directly activated via the chimney sweep button.
Manual control (7140)
Activation of manual control. If the manual control function is activated the
boiler is controlled to the setpoint manual control. All the pumps are
switched on. Additional request will be ignored!
Controller stop function (7143)
If the controller stop function is activated, the burner output set in the
setpoint controller stop is directly requested by the device.
Controller stop setpoint (7145)
With activated controller stop function the output set here is requested by
the device.
Compulsory heat draw-off DHW (7165)
This parameter is used to set that heat pumping to the domestic hot water
circuit takes priority when the chimney sweep function is active.
Off: Compulsory pumping of the heat to the heating circuits.
On: When the chimney sweep function is active, heat is pumped with
priority into the domestic hot water circuit.
Commissioning wizard (7167)
The commissioning wizard enables a guided configuration of the control
(system configuration, functions, system settings, etc.).
Telephone customer service (7170)
Here the desired telephone number of customer service can be entered.
PStick storage pos (7250)
Via the parameter PStick storage pos the data set (data set number on the
stick) can be selected which should be written or read.
If a data set is selected, the name of the data set is displayed bottom. For
backup sticks the data set name is displayed in the format
BUYYMMDDHHMM (BU for backup and date of backup: Year, Month,
Day, Hour, Minute). As soon as a data set number is selected, the text is
displayed for the data set description.
PStick command (7252)
No operation: This is the basic state. As long as no operation is active
on the stick, this command is displayed.
Reading from stick: Starts reading the data from the stick. This operation
is only possible with READ sticks. The data of the set data set is copied
to the LMS control. First a check is carried out as to whether the data
set may be imported. If the data set is incompatible, it must not be
imported. The display resets toNo operation and displays an error
message. The textReading from stick remains until the operation is
completed or an error occurs. As soon as data transmission begins, the
LMS control goes in a parameterization position. As soon as parameters
are transferred, the LMS control must be unlocked transmission has
ended. Fault 183 parameterization is displayed.
Writing on stick: Starts writing the data from the LMS control to the stick.
This operation is only possible with WRITE sticks. The data is written
into the previously set data set. Before writing of the data begins, it is
checked whether the stick has sufficient capacity for the data and that
the respective customer number is correct. The textWriting on stick
remains until the operation is completed or a fault occurs.
PStick progress (7253)
The read or write progress is displayed as a percentage. If no operation is
active or a fault occurs, 0% is displayed.
9 Settings
7703301 - 01 - 16072018
123