1. Remove screws and remove cover of the flue gas collection pan with
seal
2. Clean the heat exchanger with a brush or rinse with water
3. Remove deposits from the exhaust collection pan
4. Remove the siphon and clean it
5. Reinstall the siphon
6. Replace the cover of the exhaust collection pan
Important
Use a new seal when installing the cover.
7. Reinstall the burner
Danger
Risk to life due to explosion, fire or escaping flue gas. Before
commissioning the boiler, the parts of the system through which
fuel and flue gas flow must be checked for leaks. If there are any
leaks in the pipelines, the seals must be replaced. If there are any
leaks due to defective components, the components in question
must be replaced.
For more information, see
10.3.7 Cleaning the fan
Before the fan can be cleaned, the burner must be removed (see section
Removing the burner
).
Fig.44
Removal of the flue gas collection
pan cover
RA-0000236
1
RA-0000237
2
RA-0000238
4
10 Maintenance
7703301 - 01 - 16072018
141