DHW
Prog. no.
Level Standard value
Circulation setpoint
1663
E
55 °C
Optg mode changeover
0: None | 1: Off | 2: On
1680
E
1: Off
Consumer circuit / swimming pool circuit
Consumer
circuit 1
Prog. no.
Consumer
circuit 2
Prog. no.
Swimming
pool circuit
Prog. no.
Level Standard value
Flow temp setp cons request
1859
1909
1959
C
70 °C
DHW charging priority
0: No | 1: Yes
1874
1924
1974
E
1: Yes
Excess heat draw
0: Off | 1: On
1875
1925
1975
E
1: On
With buffer
0: No | 1: Yes
1878
1928
1978
E
1: Yes
With prim contr/system pump
0: No | 1: Yes
1880
1930
1980
E
1: Yes
Swimming pool
Prog. no.
Level Standard value
Setpoint solar heating
2055
Eu
26 °C
Setpoint source heating
2056
Eu
22 °C
Charging priority solar
1: Priority 1 | 2: Priority 2 | 3: Priority 3
2065
E
3: Priority 3
Swimming pool temp max
2070
E
32 °C
With solar integration
0: No | 1: Yes
2080
E
1: Yes
Primary contr/system pump
Prog. no.
Level Standard value
Flow temp setpoint min
2110
E
8 °C
Flow temp setpoint max
2111
E
80 °C
Syst pump on heat gen lock
0: Off | 1: On
2121
E
0: Off
Mixing valve boost
2130
E
0 °C
Actuator running time
2134
E
140 s
Primary contr/system pump
0: Before buffer | 1: After buffer
2150
E
1: After buffer
Boiler
Prog. no.
Level Standard value
Release below outside temp
2203
E
- - - °C
Full charging buffer
0: Off | 1: On
2208
E
0: Off
Setpoint min
2210
E
20 °C
Setpoint max
2212
E
90 °C
Setpoint manual control
2214
Eu
60 °C
Burner running time min
2241
E
1 min
Burner off time min
2243
E
3 min
SD burner off time
2245
E
20 °C
Pump overrun time
2250
E
2 min
Pump overr time after DHW
2253
E
5 min
Frost prot plant boiler pump
0: Off | 1: On
2300
E
1: On
Boiler pump on heat gen lock
0:Off | 1: On
2301
E
0: Off
Impact heat generation lock
1: Heating mode only | 2: Heating and DHW mode
2305
E
1: Heating mode only
Temp differential max
2316
C
- - - °C
Temp differential nominal
2317
C
15 °C
9 Settings
64
7703301 - 01 - 16072018