Config extension module
Prog. no.
Level Standard value
Function input H2/H21 module 1
0:None | 1: Optg mode change HCs+DHW | 2: Optg mode changeover DHW |
3: Optg mode changeover HCs | 4: Optg mode changeover HC1 | 5: Optg mode
changeover HC2 | 6: Optg mode changeover HC3 | 7: Heat generation lock | 8:
Error/alarm message | 9: Consumer request VK1 | 10: Consumer request VK2 |
11: Release swi pool source heat | 12: Excess heat discharge | 13: Release swi
pool solar | 14: Operating level DHW | 15: Operating level HC1 | 16: Operating
level HC2 | 17: Operating level HC3 | 18: Room thermostat HC1 | 19: Room
thermostat HC2 | 20: Room thermostat HC3 | 22: DHW thermostat | 25: Limit
thermostat HC | 29: Start prevention | 51: Consumer request VK1 10V | 52:
Consumer request VK2 10V | 58: Output request 10V
7321
C
0:None
Contact type H2/H21 module 1
0: NC | 1: NO
7322
C
1: NO
Input value 1 H2/H21 module 1
7324
E
0 V
Funct value 1 H2/H21 module 1
7325
E
0
Input value 2 H2/H21 module 1
7326
E
10 V
Funct value 2 H2/H21 module 1
7327
E
1000
Funct input EX21 module 1
0: None | 25: Limit thermostat HC
7342
C
0: None
Funct output UX21 module 1
0: None | 1: Boiler pump Q1 | 2: DHW pump Q3 | 3: DHW interm circ pump Q33
| 4: Heat circuit pump HC1 Q2 | 5: Heat circuit pump HC2 Q6 | 6: Heat circuit
pump HC3 Q20 | 7: Collector pump Q5 | 8: Solar pump ext exch K9 | 9: Solar
ctrl elem buffer K8 | 10: Solar ctrl elem swi pool K18
7348
C
0: None
Sign logic out UX21 module1
0: Standard | 1: Inverted
7349
C
0: Standard
Signal output UX21 module 1
0: 0..10V | 1: PWM
7350
C
1: PWM
Funct output UX22 module 1
See
Parameters see Funct output UX21 module 1 (prog. no. 7348)!
7355
C
0: None
Sign logic out UX22 module1
0: Standard | 1: Inverted
7356
C
0: Standard
Signal output UX22 module 1
0: 0..10V | 1: PWM
7357
C
1: PWM
Function extension module 2
0: None | 1: Multifunctional | 2: Heating circuit 1 | 3: Heating circuit 2 | 4: Heating
circuit 3 | 6: Solar DHW | 7: Primary contr/system pump
7375
C
4: Heating circuit 3
Relay output QX21 module 2
0: None | 1: Circulating pump Q4 | 2: El imm heater DHW K6 | 3: Collector pump
Q5 | 4: Cons circuit pump VK1 Q15 | 5: Boiler pump Q1 | 7: Alarm output K10 |
11: Heat circuit pump HC3 Q20 | 12: Cons circuit pump VK2 Q18 | 13: System
pump Q14 | 14: Heat gen shutoff valve Y4 | 15: Solid fuel boiler pump Q10 | 16:
Time program 5 K13 | 17: Buffer return valve Y15 | 18: Solar pump ext exch K9 |
19: Solar ctrl elem buffer K8 | 20: Solar ctrl elem swi pool K18 | 22: Swimming
pool pump Q19 | 25: Cascade pump Q25 | 26: St tank transfer pump Q11 | 27:
DHW mixing pump Q35 | 28: DHW interm circ pump Q33 | 29: Heat request K27
| 33: Heat circuit pump HC1 Q2 | 34: Heat circuit pump HC2 Q6 | 35: DHW ctrl
elem Q3 | 40: Status output K35 | 41: Status information K36 | 43: Fan
shutdown K38
7376
C
0: None
Relay output QX22 module 2
See
Parameters see Relay output QX21 module 2 (prog. no.
7376)!
7377
C
0: None
Relay output QX23 module 2
See
Parameters see Relay output QX21 module 2 (prog. no.
7376)!
7378
C
0: None
9 Settings
74