Heating circuit
1
Prog. no.
Prog. no.
3
(1)
Prog. no.
Level Standard value
Floor curing function
0: Off | 1: Functional heating | 2: Curing heating | 3:
Functional/curing heating | 4: Curing/functional
heating | 5: Manually
850
1150
1450
E
0: Off
Floor curing setp manually
851
1151
1451
E
25 °C
Floor curing setp current
855
1155
1455
E
- - - °C
Floor curing day current
856
1156
1456
E
0
Excess heat draw
0: Off | 1: Heating mode | 2: Always
861
1161
1461
E
1: Heating mode
With buffer
0: No | 1: Yes
870
1170
1470
E
1: Yes
With prim contr/system pump
0: No | 1: Yes
872
1172
1472
E
1: Yes
Pump speed reduction
0: Operating level | 1: Characteristic | 2: Temp
differential nominal
880
1180
1480
E
1: Characteristic
Pump speed min
882
1182
1482
C
40%
Pump speed max
883
1183
1483
C
100 %
Curve readj at 50% speed
888
1188
1488
E
10 %
Flow setp readj speed ctrl
0: No | 1: Yes
890
1190
1490
E
1: Yes
Operating level changeover
0: Protection | 1: Reduced | 2: Comfort
898
1198
1498
E
1: Reduced
Optg mode changeover
0: None | 1: Protection | 2: Reduced | 3: Comfort | 4:
Automatic
900
1200
1500
E
1: Protection
(1) Parameters only visible if heating circuit is installed!
DHW
Prog. no.
Level Standard value
Operating mode
Off | On
1600
Eu
On
Nominal setpoint
1610
Eu
55 °C
Reduced setpoint
1612
E
45 °C
Nominal setpoint max
1614
E
70 °C
Release
24h/day | Time programs HCs | Time program 4/DHW
1620
Eu
Time program
4/DHW
Charging priority
0: Absolute | 1: Shifting | 2: None | 3: MC shifting, PC absolute
1630
E
3: MC shifting, PC
absolute
Legionella function
0: Off | 1: Periodically | 2: Fixed weekday
1640
E
2: Fixed weekday
Legionella funct periodically
1641
E
3
Legionella funct weekday
1: Monday | 2: Tuesday | 3: Wednesday | 4: Thursday | 5: Friday | 6: Saturday |
7: Sunday
1642
E
7: Sunday
Legionella funct time
1644
E
- - - (h:min)
Legionella funct setpoint
1645
E
65 °C
Legionella funct duration
1646
E
- - - min
Legionella funct circ pump0:
Off | 1: On
1647
E
1: On
Circulating pump release
1: Time program 3/HCP | 2: DHW release | 3: Time program 4/DHW | 4: Time
program 5
1660
C
2: DHW release
Circulating pump cycling
0: Off | 1: On
1661
C
1: On
9 Settings
7703301 - 01 - 16072018
63