5.4 Replacement of the actuator

 Attention:The machine manufacturer must restrict access to the sensor 

programming mode to authorised personnel only.
Via input I3 it is always possible to replace the coded actuator with a second actuator 

at any time. By activating this input the device sets to the programming mode and the 

IN LED flashes orange; it disables all OS1, OS2, O3, O4 outputs and releases the 

actuator. With the input enabled, insert the second actuator. Acquisition of the second 

actuator is confirmed by the IN LED switching off and by four flashes of the ACT LED. 

At this point the I3 input can be disabled. The device will automatically set to restart 

and the first actuator will no longer be recognised.

The second actuator must be suitably fixed to the guard as described in paragraph 

INSTALLATION INSTRUCTIONS.

This operation must not be carried out as a repair or maintenance operation. If 

the device ceases to function correctly, replace the entire device and not just the 

actuator.

5.5 Reset input

The following error states due to a failure external to the device can be rest using the 

I3 input:

- a short circuit or overcharge of safety outputs (OS1, OS2),

- a short circuit between a safety output and the supply voltage,

- an excessive misalignment between the device and the locked actuator.

5.6 Connection in series with safety modules

It is possible to install multiple cascade-connected devices, up to a maximum of 32 

units, whilst maintaining safety category 4 / PL e according to EN ISO 13849-1 and 

integrity level SIL CL 3 according to EN 62061.

Check that the PFh

d

 value and MTTF

d

 value of the system consisting of the cascade 

of devices and the entire safety circuit meet the requirements of the SIL/PL level 

requested by the application.

Application example with single channel 

locking control function

Application example with dual channel 

locking control function

NG

NG

NG

CS

CS AM
CS FS

OS1

OS2

IS1

IS2

IS1

IS2

OS1

OS2

IS1

IS2

OS1

OS2

Ixx

Ixx

Ox

I4

VN NG-F3•

VN NG-F3•

VN NG-F3•

+ Vcc

I4

I4

NG

NG

NG

OS1

OS2

IS1

IS2

IS1

IS2

OS1

OS2

IS1

IS2

OS1

OS2

OS1

OS2

VN NG-F3•

VN NG-F3•

VN NG-F3•

+ Vcc

CS MP

Ixx

Ixx

IE1

IE2

IE1

IE2

IE1

IE2

Device with mode 1

Lock detection function (guard locked): 2 

channels / Category 4 / up to SIL 3 / PL e
Locking control function:  

1 channel / Category 2 / up to SIL 2 / PL d

Device with mode 1

Lock detection function (guard locked): 2 

channels / Category 4 / up to SIL 3 / PL e
Locking control function:  

2 channels / Category 4 / up to SIL 3 / PL e

Device with mode 2 

Interlock detection function (guard closed): 2 

channels / Category 4 / up to SIL 3 / PL e
Locking control function:  

1 channel / Category 2 / up to SIL 2 / PL d

Device with mode 2

Interlock detection function (guard closed): 2 

channels / Category 4 / up to SIL 3 / PL e
Locking control function:  

2 channels / Category 4 / up to SIL 3 / PL e

When connecting the devices in series as described above, observe the following:

- Connect the inputs of the first device in the chain to the supply voltage.

- The OS1 and OS2 safety outputs of the last device in the chain must be connected 

to the safety circuit of the machine.

- Where a safety module is used, check that the properties of safety outputs OS1/

OS2 are compatible with the safety module inputs (see paragraph INTERFACING).

- Respect the stray capacitance limits on the output lines indicated in the electrical 

data (see paragraph TEChNICAL DATA).

- Check that the response time of the cascade meets the requirements of the safety 

function to be implemented.

- The activation time of the cascade must be calculated taking into account the re-

sponse time of every single device.

5.7 Operating states

PWR 

LED

IN

LED

OUT 

LED

ACT

LED

LOCK

LED

EDM

a

Device 

state

Description

O

O

O

O

O

O

OFF

Device switched off.

green 

/ red, 

alter-

nating

green 

/ red, 

alter-

nating

green 

/ red, 

alter-

nating

green 

/ red, 

alter-

nating

green 

/ red, 

alter-

nating

green 

/ red, 

alter-

nating

POWER 

ON

Internal tests upon activation.

green

O

O

green

RUN

Safety inputs of the device not 

active.

green

green

RUN

Activation of safety inputs.

green

green / 

orange, 

alterna-

ting

O

RUN

Safety inputs incoherence. 

Recommended action: check 

for presence and/or wiring of 

inputs.

green

blinking 

red

RUN

Incoherence of solenoid acti-

vation inputs IE1, IE2. 

Recommended action: check 

for presence and/or wiring of 

inputs.

green

green

RUN

Actuator in safe area. O3 si-

gnalling output active. 

green

green

green

O

RUN

Actuator in safe area and 

locked; O3 and O4 outputs 

active.

green

green

green

green

green

O

RUN

Mode 1

Activation of safety inputs IS1, 

IS2. Actuator in safe area and 

locked. O3, O4, OS1 and OS2 

outputs active.

green

green

green

green

O

RUN

Mode 2

Activation of safety inputs IS1, 

IS2. Actuator in safe area. O3, 

OS1 and OS2 outputs active.

green

orange orange

green

green

O

RUN

Mode 3.

Actuator present, guard clo-

sed and locked, IS1 enabled, 

IS2 disabled, OS1 enabled, 

OS2 disabled

green

green

orange

green

O

O

RUN

Mode 3.

Actuator present, guard clo-

sed and not locked, IS1 and 

IS2 enabled, OS1 disabled, 

OS2 enabled

green

red, 

alterna-

ting

ERROR Error on safety outputs. Re-

commended action: check for 

any short circuits between the 

outputs, outputs and ground 

or outputs and power supply, 

then restart the device.

green

O

O

red, 

alterna-

ting

O

O

ERROR Actuator detection error. 

Check the physical integrity of 

the device and, in case of fai-

lure, please replace the entire 

device. If undamaged, realign 

the actuator with the device 

and restart the device.

red

O

O

O

O

O

ERROR Internal error. Recommended 

action: restart the device. If 

the failure persists, replace 

the device.

red, 

alterna-

ting

O

O

O

O

O

ERROR Temperature error outside the 

permissible range

green

O

green

RUN

EDM signal active (external 

relay off)

a

green

green

green

green

green

O

RUN

EDM signal not active 

(external relay on)

a

green

O

O

O

O

red, 

alterna-

ting

ERROR Error in the EDM

a

 function

O = off    

 = indifferent    (a) = available only in version NG 2•••5•••

5.8 Interfacing

Connections with CS AR-08•••• safety 

modules

Input configuration with monitored start

Connections with CS AR-05•••• / CS 

AR-06•••• safety modules

Input configuration with manual start (CS 

AR-05••••) or monitored start (CS AR-06••••)

S33

S21

S22

S35

S34

A2

S52

S12

A1

-

+

OS2

OS1

IS2

IS1

A1

 +

A2

-

NG

CS

S21

S22

S34

A2

A1

-

+

S52

S12

OS2

OS1

IS2

IS1

A1

 +

A2

-

NG

CS

Connections with CS AT-0••••• / CS 

AT-1••••• safety modules

Input configuration with monitored start

Connections with CS MF••••0, CS 

MP••••0 safety modules

The connections vary according to the program 

of the module

S33

S21

S22

S35

S34

A2

A1

-

+

S31

S12

OS2

OS1

IS2

IS1

A1

 +

A2

-

NG

CS

Ixx

Ixx

OS2

OS1

IS2

IS1

A1

 +

OS2

OS1

IS2

IS1

A1

 +

Ixx

Ixx

A2

-

A2

-

NG

NG

CS

EDM connection

 Caution: if all OS safety outputs are 

connected directly to a safety contactor, 
we recommend using fast switching diodes 
connected in parallel to the contactor coils.

OS2

OS1

I5

A1

 +

A2

-

NG 2•••5•••

-

-

KM1

KM2

Connections with expansion module CS 

ME-03••••

For NG 2•••5••• devices only

  

with mode 1 or 2

OS2

OS1

IS2

IS1

A1

 +

A2

-

NG

I5

OS2

OS1

EDM

EDM

A2

CS

Содержание NG 2D1D411C-F31

Страница 1: ...locco con attivazione ingresso I4 sblocco a molla Il principio di funzionamento D blocco a molla mantiene il blocco dell azionatore anche nel caso venisse tolta tensione alla macchina Pertanto se la m...

Страница 2: ...afiletti di media resistenza su ogni accoppiamento filettato tra pulsante prolunghe e dispositivo evitare torsioni e flessioni del pulsante di sblocco se necessario adottare un apposita guida di scorr...

Страница 3: ...icuri IS1 o IS2 non attivo Modalit 2 2 1 Le uscite di sicurezza OS devono essere disattivate quando l a zionatore non pi rilevato 2 2 Le uscite di sicurezza OS devono essere disattivate quando al meno...

Страница 4: ...e d uscita indicati nelle caratteri stiche elettriche vedi paragrafo CARATTERISTICHE TECNICHE Verificare che il tempo di risposta della cascata rispetti i requisiti della funzione di sicurezza da real...

Страница 5: ...prirsi imme diatamente Il pulsante di sblocco antipanico deve scorrere liberamente e risultare saldamente avvitato La segnaletica posta all interno della macchina che indica la funzione del pulsante d...

Страница 6: ...istanzaminimatraduedispositiviugualiperevitareradiointerferenzereciproche 2mm 8 4 Caratteristiche tecniche dispositivi di comando integrati 8 4 1 Generali Grado di protezione IP65 secondo EN 60529 Dur...

Страница 7: ...ments with inertia inaccessibility to dangerous parts actuator locked is ensured even in the event of a sudden power failure If the machine structure allows a person to enter the danger area with the...

Страница 8: ...ions and device avoid twisting or bending the release button Where necessary use an appropriate sliding guide pipe or bushing if the button and its extensions have a length greater than 100 mm tighten...

Страница 9: ...etected as released 1 2 The OS safety outputs must be disabled when the actuator is no longer detected 1 3 The OS safety outputs must be disabled when at least one of the safety inputs IS1 or IS2 is n...

Страница 10: ...ragraph TECHNICAL DATA Check that the response time of the cascade meets the requirements of the safety function to be implemented The activation time of the cascade must be calculated taking into acc...

Страница 11: ...ely and be tightly screwed in The signs placed inside the machine indicating the function of the escape release button if present must be intact clean and clearly readable 5 When the auxiliary release...

Страница 12: ...cy button 50 000 operating cycles Selector switch 300 000 operating cycles Key selector switch 50 000 operating cycles 30 000 operating cycles including removal of the key 8 4 2 Actuating force Spring...

Страница 13: ...actionneur verrouill avec lectroaimant d sexcit verrouillage ressort d verrouillage avec activation de l entr e I4 2 principe de fonctionnement E pour les versions NG 2D1E NG 2D7E actionneur verrouil...

Страница 14: ...sseur des rallonges sont disponibles pour le bouton de d verrouillage Pour une installation correcte des rallonges respecter les prescriptions suivantes Ne pas d passer la longueur totale de 500 mm en...

Страница 15: ...rature ambiante maximale ou minimale autoris e excessive une d faillance interne Les fonctions de s curit sont d finies comme suit Mode 1 1 1 Les sorties de s curit OS doivent tre d sactiv es lorsque...

Страница 16: ...e les caract ristiques des sorties de s curit OS1 OS2 sont compatibles avec les entr es du module de s curit voir paragraphe INTERFA AGE Respecter les limites de capacit parasite des lignes de sortie...

Страница 17: ...glis ser librement et doit tre solidement viss La signalisation situ e l int rieur de la machine et indiquant la fonction du bouton de d verrouillage antipanique s il est pr sent doit tre intacte pro...

Страница 18: ...raction de l actionneur typique 120 ms maximal 200 ms Distance minimale entre deux dispositifs identiques afin d viter les interf rences radio r ciproques 2 mm 8 4 Caract ristiques techniques des disp...

Страница 19: ...gelung Entriegeln durch Aktivierung des Eingangs I4 2 Funktionsprinzip E bei Ausf hrungen NG 2D1E NG 2D7E Bet tiger verriegelt bei aktiviertem Elektromagneten Verriegelung durch Aktivierung des Eingan...

Страница 20: ...ltlich Zur fachgerechten Installation der Verl ngerungen sind folgende Hinweise zu befolgen Eine Gesamtl nge von 500 mm zwischen Entsperrungstaster und Ger t darf nicht berschritten werden Verwenden S...

Страница 21: ...im ver riegelten Zustand berschreiten der maximal oder minimal zul ssigen Umgebungstemperatur interner Fehler Die Sicherheits Funktionen sind wie folgt definiert Modus 1 1 1 Die OS Sicherheits Ausg n...

Страница 22: ...rsorgung an Die Sicherheits Ausg nge OS1 und OS2 des letzten Ger ts in der Kette m ssen an den Sicherheits Kreis der Maschine angeschlossen werden Vergewissern Sie sich bei Verwendung eines Sicherheit...

Страница 23: ...es Fluchtentsperrungstasters sofern vorhanden muss unversehrt sauber und deutlich lesbar sein 5 Die Schutzeinrichtung muss sich bei bet tigter Hilfsentsperrung sofern vorhanden problemlos ffnen und di...

Страница 24: ...8 4 Technische Daten der integrierten Befehlsgeber 8 4 1 Allgemeine Daten Schutzart IP65 gem EN 60529 Mech Lebensdauer Taster tastend 1 Million Schaltspiele Not Halt Taster 50 000 Schaltspiele Wahlsch...

Отзывы: