28
HUNTER-PRO 896 Installation Guide
3.7 Relay
Output
The relay can be used for activating external devices (light, CCTV etc.) and is activated
response to alarm/fault, when entering relay code in the keypad and via telephone.
To program Relay Code refer to “HUNTER-PRO 896 User Manual”. To program relay
trip time see section
5.5.2.
Note
: If the relay timer is programmed to zero, the relay is constantly tripped until
relay code is entered or the system is disarmed.
3.8
OUT-1000: Outputs Expansion Card
OUT-1000 is an 8 TTL outputs card, used to activate peripheral devices such as CCTV,
alarm triggered lights, etc. Use the cable to connect the control panel’s JP3 connector
to OUT-1000’s JP1 connector. Follow next figure in order to connect the card to the
control panel:
R
EXPANSION CARD
SERIAL
KEYBOARD
TRANSMIT
U3
U2
C
F5
JP1
JP2
JP4
GN
D
GN
D
OU
T8
7
6
5
432
1
12
V
JP1
JP3
Figure 18 - Connecting OUT-1000 to control panel
Note
: OUT-1000 can be connected simultaneously with EXP-PRO by connecting
OUT-1000’s JP2 to EXP-PRO’s JP1 (see OUT-1000 guide for instructions).
3.9 Keypads
Reminder
: Up to 8 monitored keypads can be connected simultaneously
Connect the keypad’s wires to the PCB KEYPAD terminals.
IMPORATNT!
The 4 wires used to connect the keypad must totally be separated.
The panel’s power source (-/+) for keypads cannot be used for detectors.